Horizontal Installation Requirements:
1. The horizontal vent connector must slope upward toward the termination at least 1/4 inch per
foot and be installed so that all condensate runs back toward the appliance and is not retained in
any part of the venting system. EXCEPTION: If the system is connected to positive pressure
(Category III or IV) appliances only, terminates with a horizontal termination, and has no provision
for draining condensation and/or rain water; then the vent must pitch downward toward the
termination. This pitch must also be at least 1/4 inch per foot (2 degrees).
2. Seal weather exposed joints of the outer jacket with foil tape or an exterior grade
silicone sealant.
3. The vent system must terminate with one of the Saf-T Vent terminations or other terminations
as specified or provided by the appliance manufacturer, or approved mechanical vent devices.
4 The Termination Location:
(a) The vent must terminate at least 3 feet above any forced air inlet located within 10 feet.
(b) The vent must terminate at least 4 feet below, 4 feet horizontally from or 1 foot above AND
2 feet horizontally from any door, window or gravity air inlet into any building. Exception: Direct
Vent appliances may be listed for alternate spacing.
(c) The vent termination must be at least 12 inches above grade or, in geographical areas where
snow accumulates, at least 12 inches above the anticipated snow line.
(d) Through-the-wall vents for Category II and IV appliances and noncategorized condensing
appliances must not terminate over a public walkway or an area where condensate or vapors
could create a nuisance or hazard or could be detrimental to the operation of regulators, relief
valves or other equipment. In colder climates where ice buildup is likely to occur, Heat-fab, Inc.
will NOT be held liable for any personal injury or property damage due to any formation of ice.
(e) The vent termination must be at least 8 feet horizontally from any combustion air intake,
located above it.
5. Horizontal supports are required for every 6 feet of horizontal run and after every transition
from vertical to horizontal.
6. The total continuous
distance of the vent system
from the appliance flue
collar to the termination
must not exceed that
specified in the appliance
manufacturer’s
installation
instructions. When
venting natural draft
appliances the
termination must be at
least 5 feet above the
topmost draft hood,
otherwise a Listed
mechanical draft
inducing device
may be required.