User Manual

Heat & Glo • 6000G, 6000G-IPI • 2103-900 Rev. M • 9/08 15
2. Top Vent - Vertical Termination
No Elbow
Note: If installing a vertical vent/
termination off the top of the appli-
ance, the optional vertical termina-
tion baf e should be used.
V
1
= 40 ft. Max. (12.4 m)
V
1
= 3 ft. Min. (914 mm)
Flue Restrictor Instructions
1. Remove Exhaust Shield using a 1/4 inch nut driver by
removing the four screws securing it in place (see Figure
5.7).
Figure 5.8 Flue Restrictor
2. Break the Flue Restrictor into two pieces. Do this by
bending the part back and forth until it breaks (see
Figure 5.8).
Figure 5.6
Figure 5.7
EXHAUST
SHIELD
FLUE
RESTRICTOR
BREAK
HERE