Installation and Maintenance Instructions Saf-T Vent® CI Plus Double Wall AL 29-4C® Stainless Steel Special Gas Vent and Type L Vent For Venting Commercial & Industrial Appliances Condensing Appliances Category I,II,III,IV Appliances For Use on Positive, Neutral, and Negative Pressures up to 15" W.C. Also For Venting Listed Gas or Oil Fired Appliances Listed as Suitable For Venting With Type L Vent Low-Temperature Venting Systems Sizes: 4"- 32" Diameters.
TABLE OF CONTENTS CATEGORY 2 PAGE Introduction 3 Pre -Installation Considerations 3 General Installation Considerations 3 Definitions 4 Clearances to Combustibles 5 Horizontal Installations 6 Vertical Installations 7 Condensate Drains 8 Sealant Specification & Coverage 9 Joint Assembly Instructions, Straight Length 10 Joint Assembly Instructions, Rotating Clamp 12 Universal Boiler Adapter 15 Adjustable Section 16 Horizontal Support 17 Rain Cap 18 Exit Cone 19 Guy Support
Saf-T Vent CI Plus is a double wall Special Gas Vent that is UL Tested and Listed to the UL 1738 Standard. Saf -T Vent CI Plus is appropriate for use on Category I, II, III and IV gas fired appliances with maximum flue gas temperatures of 550°F. Non categorized condensing appliances and appliances that call for AL29-4C vent systems are also appropriate for Saf-T Vent CI Plus. Saf-T Vent CI Plus has been tested at 2 1/2 times its positive pressure rating of 15" W.C.
Definitions: AL 29-4C - A superferritic stainless steel alloy designed by Allegheny Ludlum for extreme resistance to chloride ion pitting, crevice corrosion and stress corrosion cracking. Equivalent material made by other manufacturers may be identified by the UNS designator S44735. Category I Appliance - An appliance which operates with a non-positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the appliance.
Clearances to Combustibles: Gas: Special Gas Vent DIAMETER 4” - 24" CLEARANCE TO COMBUSTIBLE MAXIMUM FLUE MATERIAL GAS TEMP.
Horizontal Installation Requirements: 1. The horizontal vent connector must slope upward toward the termination at least 1/4 inch per foot and be installed so that all condensate runs back toward the appliance and is not retained in any part of the venting system.
Vertical Installation Requirements: 1. The vent system must terminate at least 3 feet above the roof line and at least 2 feet higher than any portion of the building within 10 feet. 2. When terminated at a height of more than 6 feet the stack must be supported by a Saf-T Vent CI Plus Guy Section. 3. The vent system must terminate with one of the Saf-T Vent Terminations; except: (a) Category I or II appliances (natural draft) must use a Saf-T Vent Rain Cap.
Condensate Drains: When An Internal Condensate Drain Is NOT Part of the Appliance: • A Saf-T Vent CI Plus In-Line Drain Section or Boot Tee with a separate Drain Tee Cover is strongly recommended. Install this drain fitting as close to the appliance flue collar as possible. • A condensate drain is required for every 30 feet of horizontal vent and at/near the bottom of a vertical stack. • Use the In-Line Drain Section for a straight horizontal run.
RTV Sealant Specifications: In order to have a UL Listed system, Saf-T Vent CI Plus parts without a factory adhered seal must be installed with one of the following approved RTV sealants: M a x im um Applia nce Flue Ga s Te m pe ra ture Se a la nt Size He a t-fa b Pa rt Num be r 570° F. General Electric (GE) RTV 106 or Dow Corning 736 2.8 oz tube 10.
Joint Assembly Instructions for Straight Lengths: Note: Diameters 4" thru 16" are manufactured with a factory adhered seal on the inside of the female end and will not need sealant in the joint. 1. Begin by removing the Locking Strap and Coupler Band from the vent. Male End Locking Strap Female End Outside Coupler Band 2. Wipe the male and female ends clean with alcohol wipes.
3. Insert the male end into the female end, lining up the Locking Tabs at the same time. If needed, use pliers or vice grips to squeeze together the Tabs so they will accept the slots in the Locking Strap. When assembling elbows and tees, the male end tabs will rotate around the vent to accommodate offsets and direction changes, refer to rotating clamp installation instructions. 4. Position the Locking Strap slots over the Tabs, making sure each slot encompasses both Tabs.
Joint Assembly Instructions for Rotating Clamp: The rotating clamp allows you to position fittings in the desired flow direction of the breeching layout. Follow these instructions for Elbows, Boot Tees, Increasers and In-Line Drains, that all utilize the rotating clamp. Note: Diameters 4" thru 16" are manufactured with a factory adhered seal on the inside of the female end and will not need sealant in the joint. 1. Begin by removing the Locking Strap and Coupler Band from the vent.
3. Insert the male end into the female end of the preceding vent piece, loosen the rotating clamp on the male end of the fitting with a 5/16" nut driver. Rotating Clamp Loosen Rotating Clamp 4. Line up the tabs of the rotating clamp with the female end of the preceding vent. Insure the beads on the tabs of the rotating clamp are nested into the groove on the male end. RE-tighten the rotating clamp.
5. Position the Locking Strap slots over the Tabs, making sure each slot encompasses both Tabs. Tighten the Locking Strap with a 7/16" hollow nut driver or deep socket. CAUTION: DO NOT over tighten the clamp, as it may cause the vent to collapse. Tighten Locking Strap Detail Locking Strap Tab Detail Completed Joint 6. Center the Coupler Band around the completed joint and tighten the 7/16" nuts with a hollow nut driver or deep socket.
Saf-T Vent CI Plus Universal Boiler Adapter: The Saf-T Vent CI Plus Universal Boiler Adapter can be used horizontally or vertically to adapt Saf-T Vent CI Plus to nominal diameter flue collars. It can also adapt to flue collars that are slightly out of round. 1. Remove the clamps and coupler band from the adapter, figure 1. The adapter must clamp onto the flue collar with no less than 1 inch overlap for proper fit. Mark or scribe flue collar prior to fitting the adapter, figure 2.
Saf-T Vent CI Plus Adjustable Section: The Saf-T Vent CI Plus Adjustable Section serves as a variable length between other components when specific lengths cannot be utilized, there is a long, 13 to 20 inch, and a short, 7 to 11 inch, adjustable section. WARNING: The Adjustable Section is not designed to bear vertical force loads. Appropriate supports must be provided. Note: Vent diameters of 4” thru16” have a double sealing gasket on the inside of the outer vent, NO RTV is needed.
Saf-T Vent CI Plus Horizontal Support For Large Diameters: Saf-T Vent CI Plus must have supports for every six (6) feet of horizontal run and after every transition from vertical to horizontal. For large diameters, 24"-32" use parts numbered CCM24HZS - CCM32HZS. The support may be attached from the center bracket, figure 1 or attached to the side brackets, figure 2.
Saf-T Vent CI Plus Rain Cap: • Unscrew the wormgear clamp on the Rain Cap's Storm Collar. • Remove the locking strap from the last section of vent pipe. • Lower the Storm Collar past the clips on the last section of vent pipe. The Storm Collar should sit approximately 1/2” down from the clip edges. • Tighten the Storm Collar’s wormgear clamp to tighen around the vent pipe. • Apply a high temperature silicone sealant around the clamped edge of the storm collar. • Remove the locking strap from the Rain Cap.
Saf-T Vent CI Plus Exit Cone Termination: Use as a termination to increase the velocity of the flue gases exiting the stack. The exit cone may also help to reduce ice buildup in cold climates where a rain cap may normally be used. A narrow Finish Collar is included to seal off the 1" air space of the CI Plus vent. The Exit Cone can be attached to EZ Seal vent systems with the addition of an adapter strap, CCA__ADSV.
Saf-T Vent CI Plus Guy Support: Guy Support Assembly: Assemble the guy support to the vent sections as shown in the joint assembly instructions. Once the guy support is assembled to the vent sections, figure 1, install the 5" long coupler from the guy support so that it fits directly on top of the guy brackets. On the vent section below the guy support, attach the 8" long coupler so that it fits up to the bottom of the guy brackets, figure 2.
APPLICATION 1. To Lower A Stack (Figure 4). Attach guy wires or chains with a minimum rated capacity of 500 lbs. to the four hole locations on the guy bracket. Some lengths of stack may be assembled to go below the guy support. Feed the lengths and the guy support into the top of chase and add lengths as the stack is lowered into the chase. When lowering a stack in a square or rectangular chase, position the cable holes on the guy support in the corners of the chase.
APPLICATION 3. Support Above a Roof (Figure 6). Required if stack extends more than 6' above the roof. Note: When using a guy support above a roof, the stack below the roof must be supported. Install the guy support between the last 2 sections of straight vent. Attach guy wires or chains, with a minimum rated capacity of 500 lbs, to the four hole locations on the guy brackets. Anchor the guy lines to the top of the chase or other structure utilizing best construction methods to stabilize the system.
APPLICATION 4. Support Horizontally (Figure 8). Support horizontally by attaching guy wires, chains or threaded rod to the guy support bracket holes. Anchor the guy lines to the building infrastructure on the underside of the floor or roof. Floor or Roof Figure 7 Guy Line Guy Support 1/4" Pitch per Foot Saf-T Vent CI Plus Floor Support: Used mainly as a support between floors.
Saf-T Vent CI Plus Tall Cone Flashing with Rain Cap In Combustible Chase: APPLICATION 1. Directly On Flat Roof (figures 1 & 2). Prepare a square or round opening 4 1/2" larger than the inner vent pipe diameter, i.e. an 8" inner vent would have a 12 1/2" opening. Apply weather-stripping or outdoor caulk to the bottom of the cone plate. Attach the cone to the roof using common construction methods. Flash over the cone plate and seal the fastener heads using normal roofing requirements.
Roof Opening Framing Dimensions (figure 2): ROOF OPENING FRAMING DIMENSIONS (FIG 1 & 2) CONE PART NUMBER CCM04TCF CCM05TCF CCM06TCF CCM07TCF CCM08TCF CCM09TCF CCM10TCF CCM12TCF CCM14TCF CCM16TCF CCM18TCF CCM20TCF CCM22TCF CCM24TCF CCM26TCF CCM28TCF CCM30TCF INNER OUTER SPACING BETWEEN VENT OPENING VERTICAL DIAM A SUPPORTS (FIG 2) DIM B 4 8.5 20 5 9.5 20 6 10.5 20 7 11.5 20 8 12.5 20 9 13.5 20 10 14.5 20 12 16.5 20 14 18.5 12 16 20.5 12 18 22.5 12 20 24.5 10 22 26.5 10 24 28.5 10 26 30.5 6 28 32.5 6 30 34.
Saf-T Vent CI Plus Pitched Roof Tall Cone Flashing Directly On Pitched Roof. Prepare a square or round opening per the framing chart. Apply weatherstripping or outdoor caulk to the bottom of the cone plate. Attach the cone to the roof using common construction methods. Flash over the cone plate and seal the fastener heads using normal roofing requirements. When the vent pipe is in place through the Tall Cone, attach the Tall Cone storm collar around the pipe.
Saf-T Vent CI Plus Wall Termination: The Saf-T Vent CI Plus system can be installed through any type of wall using the Saf-T Vent CI Plus Wall Termination Assembly. The wall termination requires mechanical support from the wall sufficient to support any incidental loads on the system. If the wall is not constructed sufficiently enough to support the termination assembly, then appropriate additional framing and/or blocking is required. 1.
Maintenance Procedures: • Normal operation of gas burning appliances does not result in deposits of combustible soot in venting systems. However, a poorly adjusted or malfunctioning appliance can deposit soot and other debris which can enter the vent system. As with all vents, the Saf-T Vent CI Plus system should be inspected at least annually for the presence of deposits of soot or debris. Any such accumulation should be removed and the appliances adjusted to eliminate future accumulation.
Technical and Dimensional Data Saf-T Vent ® Appliance Adapters AL 29-4C® Stainless Steel Special Gas Vent 130 Industrial Boulevard Turners Falls, MA 01376 © Copyright 2002 Heat-Fab, Incorporated Saf-T Vent is a registered trademark of Heat-Fab, Inc. AL29-4C is a registered trademark of ATI Properties, Inc. Pub.#11701-041106 Call (800) 772-0739 Fax (413) 863-4803 www.heat-fab.
Saf-T Vent®Appliance Adapters Heat-fab Saf-T Vent adapters are compatible with all Saf-T Vent brands– EZ Seal, SC, CI, and CI Plus. A listing of Appliances by make and model with the appropriate Saf-T Vent adapter starts on page 20.
Saf-T Vent®Appliance Adapters 3" Adapters —Adapters for appliances with 3" flue collars. 9301AMTK 9301ICP 9301CRWN 9301THI 9301FUL 9301UTI Burnham (Gasketed) to Saf-T Vent EZ 9301VSMN Saf-T Vent EZ to Burnham (Gasketed) 9353BUREZ 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com Heat-fab, Inc.
Saf-T Vent®Appliance Adapters 3" Adapters —Adapters for appliances with 3" flue collars. 9301MOD 9301PAL 9302 MOD 9302PL 93PLSTEE 9301VAIL Heat-fab, Inc. 4 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.
Saf-T Vent®Appliance Adapters 3" Adapters —Adapter for appliances with 3" flue collars. 9301BSH 9301CPVC 9314SMI 9301DEL 9SF4406 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com 9SF440697 Heat-fab, Inc.
Saf-T Vent®Appliance Adapters 3" Weil-McLain Adapters —Adapters for Weil-McLain appliances. 93WMSTLH 93WMSTEE 93WMCGIS Heat-fab, Inc. 6 93WMSTLV 93WMSTXL 93WMSTRT 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.
Saf-T Vent®Appliance Adapters 4" Adapters —Adapters for appliances with 4" flue collars. 9401AMTK 9401CPVC 9401CRWN 9401DUN 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com 9401FUL Heat-fab, Inc.
Saf-T Vent®Appliance Adapters 4" Adapters —Adapters for appliances with 4" flue collars. 9401ICP 9401MES 9401JVI 9401PVI Heat-fab, Inc. 8 9401RHM 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.
Saf-T Vent®Appliance Adapters 4" Adapters —Adapters for appliances with 4" flue collars. 9414SMI 9401SRI 9401UTI 9401VAIL 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com 9401VSMN Heat-fab, Inc.
Saf-T Vent®Appliance Adapters Over-the-Flue-Collar Appliance Adapter — A generic flue collar adapter used on appliances with vent outlets that are slightly out-of-round or of irregular diameters. The split-seam design allows the adapter to clamp around irregular or inconsistent flue collars while still providing a secure connection to Saf-T Vent systems.
Saf-T Vent®Appliance Adapters Universal Boiler Adapter— Used horizontally or vertically to adapt Saf-T Vent CI Plus to nominal diameter flue collars, it can also adapt to boiler collars that are slightly out of round. The adapter comes with a joint locking strap, boiler collar clamp and a 8" coupler band.
Saf-T Vent®Appliance Adapters Flange-Type Appliance Adapter — A generic adapter used on appliances with a vent outlet that includes a bolted-on flange connection. Bolt holes and hardware are provided by the installer. Custom bolt hole patterns can be provided for an additional charge. Each Saf-T Vent CI Plus appliance adapter comes standard with a 8” long and a 5" long Saf-T Vent CI Coupler, the Saf-T Vent Ci appliance adapter comes standard with a 12" long Saf-T Vent CI Coupler.
Saf-T Vent®Appliance Adapters Aerco Adapter —Adapters for Aerco appliances. Part Number 5604AER 5802AER CCA06ADKC CCA08ADBK Nominal Diameter 6 8 6 8 Installed Length Flange Diameter 18 12 18 12 9.19 11.63 9.19 11.63 Bolt Centers 7.75 10.13 7.75 10.13 6"ID CCA06ADKC 5604AER 8"ID CCA08ADBK 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com 5802AER Heat-fab, Inc.
Saf-T Vent®Appliance Adapters Aerco Elbow Adapter —90° elbow adapters for Aerco appliances. Note: To avoid water system supply and return piping, this fitting must be rotated from the vertical position. Part Number 5814AER CCA08ADBK90 Nominal Diameter 8 8 Installed Length 12 12 Flange Diameter 11.63 11.63 Bolt Centers 10.13 10.13 CCA08ADBK90 5814AER Heat-fab, Inc. 14 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.
Saf-T Vent®Appliance Adapters Buderus Appliance Adapter — This adapter is specially designed to connect directly into the vent outlet of Buderus SB Series boilers. The hose clamp is tightened around the outside of the flue collar to create a mechanical joint. Part Number 9601SB* 9801SB 91001SB 91201SB 91401SB DIM - A Nominal Diameter 6 8 10 12 14 DIM - B Male End Crimp O.D. 7.18 7.9 9.9 11.9 13.9 DIM - C Overall Length 7.5 4.0 4.0 4.0 4.0 DIM - D Crimp Length DIM - E Maximum Clamp Diameter 1.
Saf-T Vent®Appliance Adapters Laars MightyMax Adapter — This adapter is specially designed to connect directly to the vent outlet of a Laars MightyMax Boiler. This part is supplied by Laars Heating Systems with MightyMax Boilers that require AL 29-4C® venting.
Saf-T Vent®Appliance Adapters Fulton Muffler Adapters —These adapters make the connection between Saf-T Vent products and Fulton Exhaust Mufflers. The 4" diameter has Saf-T Vent EZ Seal ends and the 6" diameter is made of heavy wall material and has non-gasketed Saf-T Vent ends. 9401FMA HS601FMA Noritz Adapter —This adapter makes the connection between Saf-T Vent products and Noritz water heaters that require 5" diameter vent.
Saf-T Vent®Appliance Adapters Raypak Boiler Adapter — This adapter is specially designed to connect directly into the vent outlet of Raypak’s ADB or High Delta boilers. The hose clamp is tightened around the outside of the flue collar to create a mechanical joint. Part Number DIM - A Nominal Diameter 9401RYPK 9501RYPK 9601RYPK 9801RYPK 9901RYPK 91001RYPK 91201RYPK 91401RYPK 91601RYPK 4 5 6 8 9 10 12 14 16 DIM - B Flue Collar I.D. 4 5 6 8 9 10 12 14 16 DIM - C Hose Clamp Diameter 4.5 5.5 6.5 8.5 9.
Saf-T Vent®Appliance Adapters Rinnai Appliance Adapters — The straight adapter, SC03AD01, or elbow adapter, SC3AD01E, is specially designed to connect directly into the vent outlet of the Rinnai Continuum model V2532. SC03AD01 Straight Adapter SC03AD01E Elbow Adapter 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.com Heat-fab, Inc.
Saf-T Vent®Appliance Adapters Appliance Makes and Models: General Notes: The following appendix includes adapters from all of Heat-fab’s Saf-T Vent brands ; EZ Seal, SC, CI, and CI Plus. Adapters are listed by the appliance manufacturer. Heat-fab Saf-T Vent adapters are compatible with all of Saf-T Vent brands pipes and fittings. CI to EZ Seal, for more details please refer to Technical Bulletin # 11719. CI or EZ Seal to CI Plus requires an adapter, refer to publication PI-CCADKT.
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Aerco International KC1000 Series (KC-1000 thru KC1000-8) 6 5604AER or CCA06ADKC 14 Benchmark (BMK 2.
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Burnham Revolution Series Series 2PV Spirit Series Independence PV Series Minuteman Series XG2000A Series 3 3 3 3 3 3 9353BUREZ 9353BUREZ 9353BUREZ Burnham Vent ONLY Burnham Vent ONLY Burnham Vent ONLY 3 3 3 Camus Dynaflame 500 Dynaflame 750,1100 Dynaflame1500, 1750 Dynaflame 2000,2500, 3000 6 8 10 12 5601BOI or CCA06ADUV 5801BOI or CCA08ADUV 51001BOI or CCA10ADUV 51201BOI or CCA12ADUV 10 & 10 & 10
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Gasmaster Industries GMI 200, 300, 400 4 5401BOI 10 GMI 600 GMI 800, 1M GMI 1.5M, 2M GMI 4M 6 8 12 18 5601BOI or CCA10ADUV 5801BOI or CCA8ADUV 51201BOI or CCA12ADUV 51801BOI or CC18ADUV 10 & 10 & 10 & 10 & Gibson see Nordyne Hatco Corporation Powermite PMG-100 & -200 4 5401BOI Hayward Pool Prod. H250IDL(P) & H400IDL(P) 6 Factory Supplied ( HF) H. B.
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Laars Heating Systems Pennant 500 (Cat I, III, & Sidewall) 6 5601BOI or CCA06ADUV 10 & 11 8 6 10 8 12 10 14 12 5801BOI or CCA08ADUV 5601BOI or CCA06ADUV 51001BOI or CCA10ADUV 5801BOI or CCA08ADUV 51201BOI or CCA12ADUV 51001BOI or CCA10ADUV 51401BOI or CCA14ADUV 51201BOI or CCA12ADUV Pennant 750 (Cat. l) Pennant 750 (Cat. lI & Sidewall) Pennant 1000 (Cat. l) Pennant 1000 (Cat.
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Modine Hot Dawg HD30 thru HD75 Hot Dawg Vent Cap Adapter 3 3 9301MOD 9302MOD 4 4 New Yorker PVCG Series (30 thru 60) 3 9353BUREZ 3 Nordyne FG6RA-045 FG6RA-060 THRU -120 FG6RA-144 FG6RAK (all models) 3 4 5 4 9363 9464 9565 9464 10 10 10 10 Noritz N-042 N-063S, N-069M, N-084M, N-084M-DV N-132 3 9301PAL 4 4 9401RYPK 18 5 9501NOR 17 Nortec GHB / GHP / GHMC 100 GHB / GHP / GHMC 200 and
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Raypak B-50 & B-130A Gas Booster Heater 3 9363 10 B-195 Gas Booster Heater Advanced Design Boiler (ADB) ADB-500 ADB-750 ADB-1000 w/out CHX ADB-1000 with CHX ADB-1500 Hi Delta 122 162, 202, 242, 302 322, 402 and 502 652, 752, and 902 992 1262 and 1532 1802, 2002, and 2072 2342 4 9464 10 6 8 9 10 12 9601RYPK 9801RYPK 9901RYPK 91001RYPK 91201RYPK 18 18 18 18 18 4 5 6 8 10 12 14 16 9401RYPK 9501RYP
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Reznor FT 30-65 BE & FE 25 -100 BE & FE 125 -250 BE & FE 300-400 4 4 5 6 9464 9464 9565 9666 10 10 10 10 Rheem Pronto! 4.2 / RTG-42 PH28 Pronto1 7.
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Takagi Flash-T-K2 Flash-T-KD20* Mobius T-M1* T-K1S, T-K2, & T-K Jr.
Saf-T Vent®Appliance Adapters Manufacturer Make & Model Flue Collar Diameter Adapter Part # Page Viessmann Vitogas 050 ECV (all models) Vitogas 100 GS10-72 Vitogas 100 GS10-84 Vitogas 100 GS10-96 Vitoden 200 WB2 6-24 & 8-32 Vitoden WB2 11-44 & 15 -60 Vertomat VSB-17, -22, -28 Vertomat VSB-37, -46, -57 Vertomat VSB-72, -89 3 8 9 10 3 4 8 10 12 9363 5801BOI or CCA08ADUV 5901BOI or CCA09ADUV 51001BOI or CCA10ADUV 9301VSMN 9401VSMN 5801BOI or CCA08ADUV 51001BOI or CCA10ADUV 51201BOI or CCA12ADUV 10 10
Saf-T Vent®Appliance Adapters Notes: Heat-fab, Inc. 30 130 Industrial Boulevard • Turners Falls, MA 01376 Phone 800 772 0739 • Fax 413 863 4803 • www.heat-fab.