Heatilator•ECO-ADV-WS22•7057-128C•August13,2010
10. Burn wood only. Other types of fuels may generate
poisonousgases(e.g.,carbonmonoxide).
11. If unit burns poorly while an exhaust blower is on in
home,(i.e.,rangehood),increasecombustionair.
12. InstallationshallbeinaccordancewiththeManufacturers
Home&SafetyStandard(HUD)CFR3280,Part24.
1. AnoutsideairinletmustbeprovidedforcombustionSee
forinstallationinformation.
2. Appliancemustbesecuredtothemobilehomestructure
attwoattachmentpointsbyboltingthepedestalthrough
hearthpadandintooor.
3. Appliance must be grounded with #8 solid copper
groundingwireorequivalentandterminatedateachend
withN.E.C.approvedgroundingdevice.
4. AppliancemustbeinstalledwithanapprovedUL103HT
ventilated chimney connector, UL103 HTchimney, and
terminalcapwithsparkarrestor.Neveruseasinglewall
connector(stovepipe)inamobilehomeinstallation.Use
onlydouble-wallconnectorpipe,Dura-VentDVL,Selkirk
metalbestosDSorSecurityDLdouble-wallconnectoror
anyListeddouble-wallconnectorpipe.
5.
InCanada,thisappliancemustbeconnectedtoa6inch
(152mm) factory-built chimney conforming to CAN/ULC-
629M,STANDARDFORFACTORYBUILTCHIMNEYS.
6. Followthechimneyandchimneyconnectormanufacturers
instructionswheninstallingtheuesystemforuseina
mobilehome.
7. Maintainclearancetocombustibles.
8. Floor protection requirements must be followed
precisely.
9. Use silicone to create an effective vapor barrier at the
locationwherethechimneyorothercomponentpenetrates
totheexteriorofthestructure.
You must use an authorized Outside Air Kit Part



NOTE:
• Offsetsfromthevertical,notexceeding45°,areallowed
per Section 905(a) of the Uniform Mechanical Code
(UMC).
• Offsetsgreaterthan45°areconsideredhorizontalandare
alsoallowed,providingthehorizontalrundoesnotexceed
75%oftheverticalheightofthevent.
• Construction,clearanceandterminationmustbeincom-
pliancewiththeUMCTable9C.Thisinstallationmustalso
complywithNFPA211.
NOTE:Topsectionsofchimneymustberemovabletoallow
maximumclearanceof13.5feet(411cm)fromgroundlevel
fortransportationpurposes.
Spark Arestor Cap
Roof Flashing
Storm Collar
Joist Shield/Firestop
Double wall
connector pipe
Floor Protector
Outside Air Floor Vent
Outside Air
Rear Vent
CAUTION!
• THESTRUCTURALINTEGRITYOFTHEMOBILEHOME
FLOOR,WALLANDCEILING/ROOFMUSTBEMAINTAINED
DoNOTcutthrough:
• Floorjoist,wall,studsorceilingtrussesoranysupport-
ingmaterialthatwouldaffectthestructuralintegrity.
WARNING! Risk of Asphyxiation!
NEVERINSTALLINASLEEPINGROOMASITWILL
CONSUMETHEOXYGENINTHEROOM.