FAQ

11
CEILING
Installation Requirements
The ideal mounting position for the HEATSTRIP
®.
Classic is on the ceiling, directly above the area to be heated. If this is
not possible, HEATSTRIP
®.
can be mounted on a wall and angled downwards. In this situation, ensure the mounting
height is in the range of 82” to 105” (2.1 m to 2.7m) and the table is within 98” (2.5m) of the wall.
For mounting heights more than 117” (3m,) we recommend the use of the optional accessories to reduce the height of the
heater to 82” to 105” (2.1 m to 2.7m.) This will increase the effectiveness of your HEATSTRIP
®.
Refer to the Mounting
Accesory section for more information.
Electrical connections/GPO’s should not be located at the back of the heater. They should be located outside the physical
footprint of the units to minimize heat build-up behind the units.
If the heater is to be mounted on an incline (eg. Vaulted ceiling), ensure the electrical connection is located at the lowest
point of the heater.
The heating surface must never be directed toward the ceiling
CEILING
CEILING
INCORRECT
INSTALLATION
CORRECT
INSTALLATION
CEILING
CEILING