Thermal Plus 6 Thermal Plus 9 Thermal Plus 12 DC Inverter Air to Water Heat Pump User’s manual Before operating this product, please read the instructions carefully and keep this manual for future use. This product may only be installed or serviced by qualified personnel. This appliance is filled with R32 refrigerant.
Catalogue 1.Before use 4 2.Introduction 11 1.1.Advanced Important Notice 4 2.1.Preliminary Information 2.2.Safety Precautions 2.3.Functioning Principles 2.4.Water pump 2.5.Product Component Diagram 2.6.Technical Specifications 11 12 14 15 18 19 3.Overview of the Units 21 3.1.Functional Diagrams 3.2.Outlines and Dimensions 3.3.Exploded Views 21 22 25 4.Assembly Configurations 27 5.
1. Before use 1.1 Advanced Important Notice Cautions: 1.Do not use means to accelerate the defrosting process or to clean,other than those recommended by the manufacturer. 2.The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating electric heater.). 3.Do not pierce or burn. 4.Be aware that refrigerants may not contain an odour. 5.
1. Before use 3) General work area All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.
1. Before use 9) Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used.
1. Before use 9.Cabling Check that cabling will not be subject to wear,corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. 10.Detection of flammable refrigerants Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks.
1. Before use 13.Charging procedures In addition to conventional charging procedures, the following requirements shall be followed. – Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. – Cylinders shall be kept upright. – Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
1. Before use the total system charge is available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
Included Accessories Below are the accessories that are included with your purchase. Please check to ensure that none are missing or damaged. If so,please contact your local distributor.
2. Introduction 2.1 Preliminary Information Thank you for your purchase of our quality heat pump. This manual is intended to provide detailed instructions for the successful installation of your newly purchased heat pump product. Please ensure that this manual, along with the User’s and Service manuals, are kept in an easy-to-access location for your reference later on.
2. Introduction 2.2.Safety Precautions To ensure both your personal safety, as well as the safety of the product, note the symbols below and be sure to understand their correlation to each of the precautions depicted. Warning Caution Prohibition User Manual The installation, dismantlement and maintenance of the unit must be performed by qualified personnel. It is forbidden to do any changes to the structure of the unit. Otherwise injury of person or unit damage might happen.
2. Introduction 2.2.Safety Precautions Fuse Steel Copper Be aware fingers might be hurt by When the power cord gets loose Please select the correct fuse or or damaged, always get a qualified breaker as per recommended. Steel the fin of the coil. person to fix it. wire or copper wire cannot be taken as substitute for fuse or breaker. Otherwise, damages maybe caused.
2. Introduction 2.3.
2. Introduction 2.4.Water Pump Pump information basic parameters Energy Efficiency Index ( EEI ) ≤0.21 Max. delivery head 9m 3 4,50 m /h Max. volume flow Power Mains connection 1~230 V +10%/-15%, 50/60 Hz (IEC 60038 standard voltage) Power (W) 3-87 Electric current (A) 0.03-0.66 Permitted field of application Temperature range for applications in HVAC systems at max. ambient temperature.
2. Introduction 2.4.Water Pump 76 G 74 115 L1 105 G 93.5 139 Type G L1 Weight mm kg 25-130/9 G11/2 130 2 25-180/9 G11/2 180 2.
2. Introduction 2.4.
Symbol Name Temp.Sensor Water pump Safety valve Kit Mixing valve Ball valve Motorized valve Water filter Expansion tank Air purging valve Symbol Note:Dotted lines mean〝able to be controlled by the Heat Pump〞. Middle temperature hot water High temperature hot water 18 Below is a general system application of the heat pump. Any specific configurations should be a variation of this “master” system drawing. All suggested assembly variations are given in Chapter 3. 2.5.
Mo d e l Ty pe Outdoor unit IP rating In d o o r u n i t tan k ve rsi o n Model Ty pe Thermal Plus 6 Air/water 6kW R32 Monobloc outdoor unit Grey IPXX Indoor unit tank v ersion IPXX Min/max heating capacity (1) El. heating power input min/max (1) C.O.P min/max (1) Min/max heating capacity (2) El. heating power input min/max (2) C.O.P min/max (2) SCOP - Av erage climate, low temperature Energy class Min/max cooling capacity (3) El. coolimg power input min/max (3) E.E.R.
Mo d e l Thermal Plus 6 Wilo Para 25-130/987/IPWM1 Mitsubishi Manuf acturer ErP approv ed circulation pump ty pe Manuf acturer ty pe Compressor Fan Sound power level Plate heat exchanger Quantity Airf low Rated power Blade diameter Fan rottation Outdoor unit Indoor unit tank version Manuf acturer Water press.
3. Overview of the Units 3.1.
3. Overview of the Units 3.2.
3. Overview of the Units 3.2.
3. Overview of the Units 3.2.
3. Overview of the Units Outside 6 5 3.3.
3. Overview of the Units 3.3.
Follow the flowchart on the right in order to locate which of the assembly configuration matches the needs of the end user, each of which contains specific assembly and wiring diagrams, with software instructions. 27 Beginning from the green “Start Here” bubble, follow the appropriate arrows to each question, which are dependent on the needs of the user. The corresponding assembly instructions will be found by turning to the page number in the end bubble.
Note: Refer to the next page for wiring and software operation instructions. Name Temp.Sensor Safety valve Kit Ball valve Water filter Air purging valve Symbol Name Symbol Water pump Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder Motorized valve distribution systems only and can be substituted by Expansion tank any other appropriate Note:Dotted lines mean〝able to be controlled by the Heat Pump〞. distribution systems.
4. Assembly Configurations - Drawing 1 Assembly 1: Wiring Diagram To achieve successful operation at a minimum, ensure the ports below are properly connected. TO OUTDOOR UNIT POWER SUP P L Y (For split uni t s ) TO OUTDOOR UNIT's Anti-f r e e z e h e a t e r (for monolock u n i t s ) Software: Basic Settings 1.Set the needed working modes of the unit via the menu 2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures: H.1.
4. Assembly Configurations - Drawing 1 Software: Basic Settings (continued) 4. Double-check to ensure that the Domestic Hot Water option is enabled under 5.
Note: For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation. Name Symbol Name Temp.Sensor Water pump Safety valve Kit Mixing valve Ball valve Motorized valve Water filter Expansion tank Air purging valve Symbol Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
4. Assembly Configurations - Drawing 2 Assembly 2: Wiring Diagram To achieve successful operation at a minimum, ensure the ports below are properly connected. Software: Basic Settings 1.Set the needed working modes of the unit via the menu 2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures: H.1.Setting a heating curve: H.2. If no heating curve is desired: C.Configuring the set water cooling temperature (if applicable): 3.
4. Assembly Configurations - Drawing 2 Software: Basic Settings (continued) 4. The location of the configuration for heating-only or cooling-only system is under 5. Double-check to ensure that the Domestic Hot Water option is enabled under 6.
Note: Refer to the next page for wiring and software operation instructions. Name Symbol Name Temp.Sensor Water pump Safety valve Kit Mixing valve Ball valve Motorized valve Water filter Expansion tank Air purging valve Symbol Notice: The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems. Note:Dotted lines mean〝able to be controlled by the Heat Pump〞.
4. Assembly Configurations - Drawing 3 Assembly 3: Wiring Diagram To achieve successful operation at a minimum, ensure the ports below are properly connected. For connection for mixing valve 2,please refers to the appendix A (on page 106-107) of this manual for more information. Software: Basic Settings 1.Set the needed working modes of the unit via the menu 2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures: H.1.
4. Assembly Configurations - Drawing 3 Software: Basic Settings (continued) 3.(cont.) Configure the water pump to operate for heating or cooling: 4. Temperature configuration options for Heating/Cooling circuit 2 are found under Please activate entire Heating/Cooling circuit 2 setting Dependent on whether cooling is needed H. configuring the set water heating temperatures: H.1. Setting a heating curve: H.2. If no heating curve is desired: C.
Note: For the cooling-only or heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating or cooling operation. Name Symbol Name Temp.Sensor Water pump Safety valve Kit Mixing valve Ball valve Motorized valve Water filter Expansion tank Air purging valve Symbol Note:Dotted lines mean〝able to be controlled by the Heat Pump〞.
4. Assembly Configurations - Drawing 4 Assembly 4: Wiring Diagram To achieve successful operation at a minimum, ensure the ports below are properly connected. For connection for mixing valve 2,please refers to the appendix A ( on page 106-107 ) of this manual for more information. Software: Basic Settings 1.Set the needed working modes of the unit via the menu 2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures: H.1.
4. Assembly Configurations - Drawing 4 Software: Basic Settings (continued) 3.(cont.) Configure the water pump to operate for heating or cooling: 4. The location of the configuration for heating-only or cooling-only system is under H. configuring the set water heating temperatures: H.1. Setting a heating curve: H.2. If no heating curve is desired: C. Configuring the set water cooling temperature (if applicable): 5.1.
Note: For the heating-only circuit, a motorized two-way valve can be connected to the unit, to cut the water supply during heating operation. Name Symbol Name Temp.Sensor Water pump Safety valve Kit Mixing valve Ball valve Motorized valve Water filter Expansion tank Air purging valve Symbol Notice : The Fan Coil Unit, Floor Heating System, and Radiator are placeholder distribution systems only and can be substituted by any other appropriate distribution systems.
4. Assembly Configurations - Drawing 5 Assembly 5: Wiring Diagram To achieve successful operation at a minimum, ensure the ports below are properly connected. For connection for mixing valve 2,please refers to the appendix A ( on page 106-107 ) of this manual for more information. Software: Basic Settings 1.Set the needed working modes of the unit via the menu 2.Temperature configuration options for Heating/Cooling circuit 1 are found under H.Configuring the set water heating temperatures: H.1.
4. Assembly Configurations - Drawing 5 Software: Basic Settings (continued) 3.(cont.) Configure the water pump to operate for heating or cooling: 4. Temperature configuration options for Heating/Cooling circuit 2 are found under H. configuring the set water heating temperatures: H.1. Setting a heating curve: H.2. If no heating curve is desired: C. Configuring the set water cooling temperature (if applicable): 4.1.
5. Installation Walkthrough 5.1. Sanitary Hot Water Configurations 5.1.1. Note about the Heating/Cooling Distribution System Users are heavily recommended to install a buffer tank into the chosen configuration, especially when the method of hot water distribution is below 20L/W of water volume. The buffer tank should be installed between the heat pump and the distribution system, in order to: • Ensure the heat pump unit provides a stable and sufficient water flow rate.
5. Installation Walkthrough 5.2. Heating and Cooling Circuits This heat pump unit is capable of controlling two completely different heating and cooling circuits, as shown in the following images. Configuring the temperatures for circuits 1 and 2 can be done via the “Heating and Cooling Circuit” menus. If only one circuit is desired, then “Heating and Cooling Circuit 2” can be set to OFF. 5.2.1.
5. Installation Walkthrough 5.2. Heating and Cooling Circuits 5.2.2. Mixing Valves MV1 and MV2 If the system water temperature may be higher (or lower) than the temperatures needed for circuit 1 (or circuit 2) in a heating or cooling operation, then a mixing valve can be added to the circuit, and connected to the MV1 (or MV2) port on the indoor unit.
5. Installation Walkthrough 5.2. Heating and Cooling Circuits 5.2.3. Circulation Pump Control Note: P1 is circulation pump 1, P2 is pump 2 • “Buffer Tank” should be checked if one is installed between the heat pump and distribution system. • “P1/P2 for Heating/Cooling Operation” sets that circuit’s pump to work for heating or cooling. If “Buffer Tank” is NOT checkmarked, both P1 and P2 will only work when the compressor is working in the same mode that the pump is set to.
5. Installation Walkthrough 5.3. Indoor Unit Installation 5.3.1. Choosing an installation location A. The indoor unit can be located in a room, corridor, balcony, garage or warehouse. B. Indoor unit should be placed on flat and solid ground. C. The unit is recommended to be put in a space close to water supply, and drainage. D. The outdoor and indoor unit should be placed close, to save the copper tube as well as the energy. E. The indoor unit shall be placed in dry and well-ventilated environment. F.
5. Installation Walkthrough 5.4. Outdoor Unit Installation 5.4.1. Choosing an installation location A. The outdoor unit can be located in a room, corridor, balcony, and roof or hanged on the wall. B. Please don't install outdoor unit close to bedroom or living room, because there is some noise when it's running. C. The outdoor unit shall be placed in dry and well-ventilated environment. D. Outdoor unit mustn't be installed in an environment where volatile, corrosive or flammable liquid or gas exists. E.
5. Installation Walkthrough 5.4. Outdoor Unit Installation Please add rubber absorber under the outdoor unit, to reduce the vibration. 【A. On a concrete stand】 1.The unit must be located on a flat,solid,preferably cemented surface. 2.When installing the unit,introduce a tilt of 1cm/m for rain water evacuation. 3.When installing the unit in harsh climatic conditions,sub-zero temperature ,snow,humidity.., it is recommended to raise the unit off the ground by about 50cm. 4.
5. Installation Walkthrough 5.5. Water pipe connection 5.5.1.Amount of Refrigerant: Before connect the water piping between indoor and outdoor unit, please notice the size of water connector, and should choose the proper size of water piping, to avoid leakage. G1"male G1"male 5.5.2.Precautions: • Choose the proper water piping, which can afford the max. pressure from the city water system. • Insulate the pipe before connecting it.
5. Installation Walkthrough 5.5. Water pipe connection After installing the unit, please connect the water inlet and outlet pipe according to the local instructions. Please carefully select and operate the water pipe. After connection, the water piping should be pressure tested, cleaned before use.
5. Installation Walkthrough 5.6. Installation of the kits in the accessories 3.Drain the water to drainage system of the house, and open the ball valve to drain out all water inside the tank. Please extend the drainage pipe by connecting another water pipe, if the distance between the unit and drainage system is long. Connect to drainage system of the house 【Insulation】 All pipes running hot water should be well insulated.
5. Installation Walkthrough 5.6. Installation of the kits in the accessories 【L type decorative panel in back side】 When the pipings are installed in back side of the unit, L type decorative panel can be installed as follows, in order to hide the pipings in backside and look better: 1. Take out 2pcs L type decorative panel in back side 1 and 1pcs L type decorative panel in back side 2. 2. Find 14 screws holes in the picture 2. 3.
5. Installation Walkthrough 5.7. Wiring 5.7.1. Explanation of Terminal Block 1 For user's side A E A: Unit power supply This should be connected directly to the city power supply. For all units, ensure that a cable of sufficient gauge is used. (found on nameplate) E:Power supply for anti-freeze electric heater in outdoor unit This power supply is from indoor unit to anti-freeze electric heater in outdoor unit.
5. Installation Walkthrough 5.7. Wiring 5.7.2.
5. Installation Walkthrough 5.7. Wiring 5.7.3. Explanation of Terminal Block 3 COM CS COM HS Application Side E F TO OUTDOOR UNIT COMMUNICATION 2*0.75mm² SHIELDED A A: Signal cable between indoor and outdoor unit. B,C: Motorized Water mixture valve 1&2: As explained in System illustration chapters, this unit can have two water mixture valves for distribution system under its control.
5. Installation Walkthrough 5.7. Wiring 5.7.4. Wiring Process Preliminary Precautions • • • • • • • • Please ensure that a suitable circuit breaker is used for the heat pump. The power supply to the heat pump unit must be grounded. Wiring should be done by a licensed professional, and comply with industry regulations. The unit should be completely powered off before any wiring is done. Cables should be properly fastened into place, to prevent loosening from occurring.
5. Installation Walkthrough 5.7. Wiring 5.7.5. Wiring Process 1) Open the indoor unit’s front panel and remove the electrical box cover. 【Connect of drainage pipe】 When the tank need to be drained, please do as per following instruction: Screw Screw 1.Unscrew the 3pcs screws on top of front panel. Disconnect the quick connector. 2.Hold the front panel up by 10~15mm, disconnect the quick connector from wired controller, and then take out the front panel. 3.
5. Installation Walkthrough 5.7. Wiring 3) Connect the signal cable between the indoor and outdoor unit: Retrieve the signal cable from the accessories bag. 4) Connect the Plate electrical heating power cord between the indoor and outdoor unit . B B corresponding with each other A B A A C A. Insert one end of this cable through the cable gland on the top of the indoor unit, and connect it to A and B on the appropriate terminal block. B. Fasten the cable gland to ensure the cable won't get loosen. C.
5. Installation Walkthrough 5.7. Wiring 5) Tc (cooling&heating water temperature sensor) and Tr (room temperature sensor) are pre-connected and put inside the indoor unit. Following below instructions if they need to be moved to another place. Sensor cable connection Indoor PCB ●Retrieve all sensors and communication cables from the accessories bag. ●Connect all sensors to the communication cables, and insert the male end into the indoor unit through the cable glands.
5. Installation Walkthrough 5.8. Attention A.The user mustn't change the structure or wiring inside the unit. B.The service and maintenance should be performed by qualified and well-trained technician. When the unit fails to run, please cut off power supply immediately. C.The smart control system can automatically analyze various protection problems during daily use, and display the failure code on the controller. The unit may recover by itself.
5. Installation Walkthrough 5.9. Test run After installation finished, please fulfill the water system with water and purge out air in the system before start-up. 5.9.1. Before start-up The list of verifications below must be performed before the unit starts up, to ensure best possible conditions for smooth long-term operation. The list is not exhaustive, and should only be used on a minimum reference basis: 1) Make sure the fans are rotating freely. 2) Confirm correct flow directions in water piping.
6. Introduction Of Operation Panel B. Working mode C. Functions A. Communication symbol D. Warning START ENGING STOP 26℃ E. ON/OFF 15℃ F. Touch screen panel 34.7℃ 23.9℃ ℃ 6.8℃ G. Mode H. Setting A. Communication symbol When this symbol is in blue, it means communication is working correctly. When this symbol is in grey, it means communication is broken. B. Working mode Working mode switching symbol is ON when system working mode is under switching.
6. Introduction Of Operation Panel D. Warning When the unit is having a protection or failure, a symbol will be shown on the display. Please enter into "Info" menu to check the protection or failure codes. Yellow——Outdoor unit protection or failure Red——System protection or failure Some information, protections and failures that are more likely to happen, will shown in front page so the customers can see it easily: 1. Coil Temp. Too Low This is indoor coil temperature too low.
6. Introduction Of Operation Panel 5. Serial Port Connect Error Serial port connect error means the communication between operation panel and indoor PCB or outdoor PCB hasn't been set up successfully. Check the cable connection in between. Check whether the last three switches on outdoor power PCB are set to 001; whether last three switches on indoor PCB are set to 001. Unit recovers when communication recovers. 6. Cooling Water Temp. Too Low Compressor stops if water outlet is too low in cooling mode.
6. Introduction Of Operation Panel START ENGING STOP 23.9℃ 34.7℃ F. Touch Screen Panel 6.8℃ Set water temperature Current water temperature 26℃ 15℃ Set mode 35℃ Room temperature 40℃ Set water temperature 23.9℃ 34.7℃ ℃ 6.8℃ Ambient temperature Water tank temperature G. Mode Press to switch unit working mode(Heating, Cooling, Hot water, Auto).In Auto mode, unit switch its working mode between cooling, heating and sanitary hot water automatically according to setting.
6. Introduction Of Operation Panel H. Setting: Press to enter into setting menu 3. DHW settings - see page 72 2. Heating/Cooling circuit 2 - see page 71 See page 92 See page 91 1. Heating/Cooling circuit 1 - see page 68 4. DHW Storage - see page 74 5. Reduced Setpiont for Heating - see page 76 8. User Management - see page 79 6. Anti-Legionella Function - see page 77 7. Vacation Mode - see page 78 10. Backup Heating - see page 83 11. Water Pump Settings - see page 85 See page 91 See page 92 9.
7. Operation Instruction 1. Heating/Cooling Circuit 1 1. Heating & Cooling Settings 1, HC/CC 1 1.01) Heating or Cooling Stops based on Water ∆T 1.02) Heating or Cooling Stops based on Water ∆T ◆ 1.01: This is to set a temperature to stop unit. Unit stops operation when [ Tset+ 1.01] in heating operation, or [Tset–1.01] in cooling operation is reached. ◆ 1.02: This is to set a temperature to re-start unit. Unit starts operation again when water temp. drops below [Tset-1.
7. Operation Instruction 1.03 △T Compressor Speed-Reduction This parameter is used to set a temperature, at which compressor starts to slow down its speed. Also, the set value is based on ΔT. Compressor always works with its maximum allowable speed, if actual water temperature is lower than [ Tset-1.03 ](in heating mode) or higher than [Tset+1.03](in cooling mode). When actual temperature is between [Tset-1.03,Tset] ιν heating mode or [Tset, Tset+1.
7. Operation Instruction Parameter 1.06~1.10 is used to set 5 different ambient temperatures; while parameter 1.11~1.15 is used to set 5 corresponding set water temperatures VS these 5 ambient temperatures. Then the controller will create a heating curve according to these settings, and try to reach the set water temperature automatically according to actual ambient temperature.
7. Operation Instruction 2. Heating / Cooling Circuit 2 2.01 Heating&cooling Circuit 2 Set whether the system has the second circuit . 2.02 Set Temp For Cooling Set the set temperature for cooling operation of circuit 2. 2.03 Set Temp For Heating If heating curve function is disabled for circuit 2, a fixed value of set water temperature in heating mode can be set here. 2.04 With/Without Mixing Valve 2 Set whether circuit2 has a mixing valve connected. For more details, please refers to chapter 2.1.5 2.
7. Operation Instruction 3. DHW Settings 3.01 Setpoint DHW Set temperature for sanitary hot water. 3.02 DHW Restart ∆T Setting Heat pump unit will start working for sanitary hot water again, after temperature drops below Tset-3.02 here. 3.03 Shifting Priority Turn ON/OFF this function. Air to water heat pump is an equipment that absorbs heat from surrounding air, and transfers it to water. The lower the ambient temperature is, the less heat the unit absorbs.
7. Operation Instruction If shifting priority function is ON, and ambient temperature is lower than [3.04],unit works as shown below: House heating water under water temperature The running time for DHW is cleared. Unit Starts heating and counting the running time. YES Unit keep on working in DHW and counting the running time. NO NO The ambient temp. Is below (3.04) Whether the YES Whether unit works YES in DHW over (3.
7. Operation Instruction 4. DHW Storage Sanitary Hot Water Storage Function After showers, house usually needs only medium temperature sanitary hot water in day time. This function is used to store high temperature sanitary hot water in low demand time (mid-night, or day time of working days), and reheat the water to medium temperature out of this time period. 4.01 Sanitary Hot Water Storage Function Turn ON/OFF this function. 4.
7. Operation Instruction 4.05 Reheating Set Temp. Set a lower set value for DHW operation. Unit will work with this set value when reheating function is activated in the set time period (time period set in parameter 4.04). 4.06 Reheating Restart ∆T Setting Set “reheat restart”water ∆T. When water tempe rature drops below ∆T based on reheat set tempe rature within the set reheating time period, unit restarts.
7. Operation Instruction 5. Reduced Setpoint For Heating Reduced Setpoint Function: Sometimes the house heating demand maybe lower than normal, like during sleep period or working time. In this way, a reduced value based on standard set value can be set here for better efficiency of the whole system. Quiet Operation: Also, for a better noise issue, a Quiet Operation can be also set in this menu.
7. Operation Instruction 6 . Anti-Legionella Function If user uses sanitary hot water directly out from the HWT (hot water tank), for the health purpose, it’s requested that he needs to heat up the water inside the tank over 60℃ for anti-legionella purpose once a week. Note:Please always refers to local regulation for a correct usage of this function. 6.01 Anti-Legionella Program Turn ON/OFF Anti-Legionella function. 6.
7. Operation Instruction 7. Vacation Mode If you need to be away from house for some days, you can use this Vacation Mode function to reduce the set temperatures for both sanitary hot water and house heating , to save more energy. 7.01) Vacation Mode Turn ON/OFF Vacation Mode. 7.02) Sanitary Hot Water Temp. Drop During Vacation Mode Set a temperature drop for sanitary hot water based on standard DHW set value during the set time period for vacation mode. 7.03)Heating Water Temp.
7. Operation Instruction 8. User Management 8.01) Permission Level For the safety of the product,some parameters can only be adjusted under installer' s permission level. The permission level can be changed in this menu. A password is needed for activating the installer's permission level. 8.02) Heating/Cooling ON/OFF Timer To turn ON/OFF the timer function for heating/cooling operation. 8.03) Heating/Cooling ON/OFF Timer Set the ON and OFF timer for the heating/cooling operation.
7. Operation Instruction 8.04) Language Set system language. 8.05) Set Date and Time Set system clock date and time. 8.06) Distribution System Setting The unit is default set to have 3-way motorized valve inside the unit, which has different flow directions for sanitary hot water/cooling+heating mode. If user needs to have sanitary hot water and heating on the same distribution system, he can set this parameter to“Hot Water+Heating/Cooling”.
7. Operation Instruction 9. Mode Settings 9.01) Sanitary Hot Water Set whether the system has sanitary hot water circuit or not. When unit works in Sanitary Water mode, 3-way motorized valve will guide water to HWT automatically. 9.02) Heating Set whether the system has water circuit for house heating purpose or not. When unit works in heating mode, 3-way motorized valve will guide water to heating circuit automatically. 9.
7. Operation Instruction 9.05) Max Allowed Duration For Min Compressor Speed When unit output is higher than demand,compressor speed will be reduced.If compressor has continuously worked in minimum compressor speed for over time set via“Max Allowed Duration For Min Compressor Speed”,unit stops. 9.
7. Operation Instruction 10. Backup Heating Electric heater for DHW, 500W (not HWTBH) 250L D.H.W Tank AH HBH 3KW 3KW ◆ AH---Aux iliary Heater inside the indoor unit ◆ HBH---Heating Back-up Heater ◆ HWTBH ---Hot Water Tank Back-up Heater HWTBH is external back up heater for DHW. If it is connected to "HWTBH signal" in wiring diagram, HWTBH can be controlled by heat pump controller. 10.01) Backup Heating Sources For Heating Set whether the system has HBH (Heating Back-up Heater). 10.
7. Operation Instruction This is for adjusting how fast Backup Heating Sources for heating operation will be turned ON if heat pump unit can't provide enough power. The bigger the value is set, longer time it takes to start the Backup Heating Sources if heat pump capacity is not enough. 10.06) Water Temperature Rise Reading Interval Time interval for checking the temperature increase when unit works in DHW mode.
7. Operation Instruction 11. Water Pump Settings 11.1) Circulation Pump P0 Type This is to set the type of circulation pump inside the unit, P0. 11.2) Speed Setting of Circulation Pump P0 This is to set the working speed of circulation pump inside the unit, P0. 11.3) Working Mode of Circulation Pump P0 This is to set the working mode of circulation pump for cooling/heating operation inside the unit, P0. P0 can work as the following settings: 1. Interval working mode.
7. Operation Instruction 12. Floor Curing After initial Installation or Long Time Non-operation, a floor heating system may be very wet in the concrete. Most of the heating capacity from heat pump unit is consumed to dry up the water in the concrete for its evaporation. This floor curing function is used to dry the floor to ensure the safety of heat pump system. 12.1) Floor Curing Turn ON/OFF this function.
7. Operation Instruction 13. Electrical Utility Lock Some electricity companies offer a special rate to the houses who lowered their power consumption during peak time. When peak time comes, electricity company will send an ON or OFF signal to every house, indicating that they hope the house owners to turn OFF some electric equipments. This system can be connected to the unit if the unit is supposed to stop working during this period, and use the following parameter settings to activate this function. 13.
7. Operation Instruction 14. Other Options 14.1) Motorized Diverting Valve Switching Time Set how many minutes as switching time of the motorized diverting valve spending on switching the water flow fully between DHW and Heating/Cooling circuit. Note: This parameter must comply with the motorized diverting valve. Otherwise unit may not be able to work due to not enough water flow rate. 14.
7. Operation Instruction 14.6) Ambient Temp. to activate first class anti-freezing 14.7) Ambient Temp. to activate second class anti-freezing 14.8) Ambient Temp. to stop second class anti-freezing 14.9) Water Temp. to activate second class anti-freezing 14.10) Water Temp. to stop second class anti-freezing These parameters are used for setting the anti-freezing protection of the unit in winter time, when unit is powered but turned OFF.
7. Operation Instruction 15. Unit Real-time Data This menu is designed for viewing the running data of the system. Following parameters that are related to the working of the system can be viewed in this menu: 01): Control System Version No 02): Database Version 03): Heat Exchanger Water Outlet Temperature-Indoor - Tuo 04): Heat Exchanger Water Return Temperature-Indoor - Tui 05): Indoor Coil Temp. - Tup 06): Sanitary Hot Water Temp.- TW 07): Cooling/Heating Water Temp.
7. Operation Instruction Info Press "Info" to view water system and water system working status.
7. Operation Instruction Home Home: Press this button at any page, operation panel goes back to home page. START ENGING STOP 26℃ 15℃ 34.7℃ 92 23.9℃ 6.
8. Electric Heater This unit has included two electric heaters inside. Two electric heaters are used to keep the water temperature when heat pump capacity is not enough or heat pump fail to work, as well as heat the water up more rapidly when water temperature is low. 【500W electric heater】 1. 500W electric heater only can be controlled by digital thermostat. 2. Power supply is 230V/50Hz/1Ph, and temperature setting range is 30~75℃. 3.
8. Electric Heater When heat pump capacity is not enough, or heat pump meets a failure, indoor PCB will turn ON the internal heater automatically. However, if the indoor PCB itself is broken, one can obey the following instructions to turn ON the heater manually: 2 1 Emergency switch K1 Mechanical thermostat Switch ON the switch K1 inside the unit, as shown in below picture. Unscrew three screws on top, and lift the front panel up by around 20mm, then remove the front panel.
9. Failure Code 【Outdoor】 Type Code Description Blinking times Main line current protection 1 Compressor phase P02 current protection 2 IPM module P03 protection 3 Compressor oil P04 return protection 4 P01 Compressor shut down due to high/ low pressure switch P05 open caused by abnormal high/low Protection pressure 5 Compressor speed down due to abnormal high P06 pressure detected by condensing pressure sensor 6 Compressor P07 preheating 7 Compressor P08 discharge temp.
9. Failure Code Type Code Description Compressor speed down due to abnormal low Protection P14 pressure detected by condensing pressure sensor Failure Outdoor ambient F01 temp. sensor failure Outdoor evaporator F02 coil temp. sensor failure Compressor F03 discharge temp. sensor failure Outdoor Suction F04 temp.
9. Failure Code 【Indoor】 Type Code F13 F14 F15 F16 F17 F18 Failure Description Room temp. sensor failure Sanitary hot water temp. sensor failure Cooling/heating water temp. sensor failure Unit water outlet temp. sensor failure Unit water inlet temp. sensor failure Indoor coil temp.
9. Failure Code Type Code Description S04 Communication failure S05 Serial port connect error Blinking times Water outlet Temp. S07 too high protection in heating/hot water Water outlet Temp. S09 too low protection in heating/hot water Too small water flow S10 rate failure If unit stops due to “too small water flow rate”protection code(S02) over three times in certain period of time, unit stops and gives S10 Compressor stops failure code. It can only be recovered by re-powering the unit.
10. Attention A.The user mustn't change the structure or wiring inside the unit. B.The service and maintenance should be performed by qualified and well-trained technician When the unit fails to run, please cut off power supply immediately. C.The smart control system can automatically analyze various protection problems during daily use, and display the failure code on the controller. The unit may recover by itself. Under normal operation, the pipings inside the unit don't need any maintenance.
11. Service 【 Indoor unit】 Service on indoor unit as follows: (this operation must be done by qualified personnel) 1. Cut off the power supply 2. Remove the front panel(Be care about the cables in between) 3. Check the electric part 3 1 2 【Outdoor unit】 1.Maintenance of controller a. Cut off the power supply. b. Disconnect all cables. c. Unscrew 4 screws, you can take this controller off.
11. Service 【Indoor PCB】 2 1 1. LED indicator light on Indoor PCB ON 2. Dip switch on indoor PCB Factory Default Setting: OFF 【Outdoor PCB】 2 1 1.Dip switch on outdoor PCB Factory Default Setting ON 2.
11. Service 2. Replacement of fan motor a. Take off screws of the front grill (see picture a and b). b. Use a wrench to loosen the nut for fan blade and take out the fan blade(see picture c and d). c. Unscrew the screws of fan motor (see picture e). d. Then unscrew the small handle (see picture f). a c b Front grill d f e Fan blade Fan motor e. Tracking and take out the ground and power cable for fan motor, and take the whole fan motor with cables out. (see picture g, h, i and j). f.
12. Maintenance 4. Replacement of temperature sensor a. Take off the back panel (see picture a). b. Take out the broken sensor from its fixture, and also pull its connector out from the controller. c. Put the new sensor back and connect it to the same port on controller. a b c Back panel Sensor connector Temperature sensor 【Cleaning of water filter】 The water filter should be cleaned according to the manual of water filter, to ensure the water flow of the water system.
12. Maintenance 【Gas Charging】 The refrigerant plays an important role in delivering energy in cooling or heating. Insufficient refrigerant affects directly efficiency of cooling and heating. Please pay attention to the following before adding refrigerant: A. The work should be done by professionals B. Please make sure the copper pipe has no leakage before gas charging. If the copper pipes has leakage, please repair or change the pipes firstly. C.
13. Trouble-shooting Failure Cause 1. No power supply 2. Fuse is broken or circuit breaker is disconnected Unit can’t start up Fan fails to run Low heating performance 3. Some kind of protection works 5. compressor fails 5. Change a compressor 1. Fan motor wire loose 1. Check the wire connections. 2. fan motor failure 2. Change fan motor. 1. The coil fins are very dirty 1. Clean the evaporator coil 2. Air inlet is blocked 2. Remove any object that blocks the air circulation of the unit. 3.
14.
14.
15. Appendix B: Wiring Indoor —— 1 08 TAKE CARE! The specifications are subject to change without prior notice. For actual specifications of the unit, please refer to the specification stickers on the unit.
15. Appendix B: Wiring Outdoor —— 1 09 TAKE CARE! The specifications are subject to change without prior notice. For actual specifications of the unit, please refer to the specification stickers on the unit.
Thank you for purchase of our quality product. Please read this manual thoroghly before use , and follow the instructions carefully in operating the unit in order to prevent damages to either the device or persons. Please refer to the contact information below for technical support and enquiries: Product specifications are subject to change with improvements , E-mail: without prior notice. Please refer to the specification sticker on the unit for the most recent specifications.