Data Sheet

HELUTHERM
®
120
flexible,heat-resistant(+105°C),metermarking
PropertiesCablestructureTechnicaldata
Barecopperconductor,to
DINVDE0295cl.5,finewire,
BS6360cl.5,IEC60228cl.5
SpecialPVCcablewithincreased
heat-resistanceadaptedto
DINVDE0285-525-2-11/
DINEN50525-2-11
0,5-0,75mm²acc.toIEC60227/56
1,0-2,5mm²acc.toIEC60227/57
Thematerialsusedinmanufactureare
cadmium-freeandcontainnosilicone
andfreefromsubstancesharmfulto
thewettingpropertiesoflacquers CoreinsualtionofspecialPVC
compoundtypeTI3to
DINVDE0207-363-3/DINEN50363-3
Tests
PVCself-extinguishingandflameretardant
acc.toDINVDE0482-332-1-2,
DINEN60332-1-2,IEC60332-1(equivalent
DINVDE0472part804testmethodB)
CoreidentificationtoDINVDE0293-308
-upto5corescoloured
-from6cores,blackwithcontinuous
whitenumbering
Temperaturerange
flexing-5°Cto+105°C
fixedinstallation-30°Cto+105°C
(forshorttime+120°C)
Note
GN-YEconductor,3coresandabove
intheouterlayer
Nominalvoltage
0,5-1mm²U
0
/U300/500V
from1,5mm²U
0
/U450/750V
G=withgreen-yellowconductor
x=withoutgreen-yellowconductor
Coresstrandedinlayerswith
optimallay-length
Spark-test 6000V
AWGsizesareapproximateequivalent
values.Theactualcross-sectionisinmm².
OutersheathofspecialPVC,heat-
resistantcompoundtypeTM3to
DINVDE0207-363-4-1/DINEN50363-4-1
Testvoltage 2000V
Breakdownvoltagemin.4000V
Onrequest
HELUTHERM
®
120H03V2V2-F
HELUTHERM
®
120H05V2V2-F
HELUTHERM
®
120(H)05V2V2-F
Insulationresistance
min.20MOhmxkm
Outersheathblack(RAL9005)
alsoavailableinothercoloursonrequest
Minimumbendingradius
flexing7,5xcableØ
fixedinstallation4xcableØ
withmetermarking
Radiationresistance
upto80x10
6
cJ/kg(upto80Mrad)
Application
Thermcablesareidealforuseinmachines,appliancesormotorswhicharesubjecttodirectcontactwithhightemperatures(e.g.varnishingmachines
anddryingtowersetc.).Forapplicationindry,moistandwetroomsandinopenair.
=TheproductisconformedwiththeECLow-VoltageDirective2006/95/EC.
AWG-No.Weight
app.kg/km
Cop.
weight
kg/km
OuterØ
app.mm
No.coresx
cross-sec.
mm²
Partno. AWG-No.Weight
app.kg/km
Cop.
weight
kg/km
OuterØ
app.mm
No.coresx
cross-sec.
mm²
Partno.
2040,09,64,82x0,524002 1677,029,07,22x1,524030
1697,043,07,83G1,5240312050,014,45,13G0,524003
2060,019,25,54G0,524004 16122,058,08,54G1,524032
16143,072,09,65G1,5240332070,024,06,25G0,524005
2090,033,66,77G0,524006 16179,0101,010,67G1,524034
16310,0173,014,112G1,52403520140,058,09,012G0,524007
20170,086,010,718G0,524008 16460,0259,017,018G1,524036
16650,0360,020,225G1,52403720250,0101,012,625G0,524009
14120,048,08,62x2,5240391952,014,45,32x0,7524011
1961,021,65,63G0,7524012 14150,072,09,33G2,524046
14200,096,010,44G2,5240401975,029,06,34G0,7524013
1994,036,06,95G0,7524014 14250,0120,011,45G2,524041
14310,0168,012,67G2,52404219112,050,07,77G0,7524015
19180,086,010,012G0,7524016
12180,077,010,02x424044
19270,0130,012,218G0,7524017
12220,0115,010,83G424291
19380,0180,014,325G0,7524018
12300,0154,012,04G424045
1850,09,63,51x124019 12360,0192,013,45G424292
1860,019,25,62x124020
1873,029,06,13G124021
1888,038,06,64G124022
18110,048,07,55G124023
18121,058,08,16G124024
18130,067,08,17G124025
18223,0115,010,812G124026
18350,0173,012,918G124027
18485,0240,015,425G124028
Dimensionsandspecificationsmaybechangedwithoutpriornotice.(RE01)
23.11.2017/Dimensionsandspecificationsmaybechangedwithoutpriornotice.