Datasheet

HELUTHERM
®
145
flexible,cross-linked,halogen-free
PropertiesCablestructureTechnicaldata
Tinnedcopperconductor,to
DINVDE0295cl.5,finewire,
BS6360cl.5,IEC60228cl.5
Halogen-freesinglecoreswithincreased
heatresistance
Lowerpropagationoffire
Lowdevelopmentofsmokeandfumes
Temperaturerange
flexing-35°Cto+120°C
fixedinstallation-55°Cto+145°C
Goodabrasionandnotchresistance
Coreinsulationofpolyolefin-copolymer
cross-linkedandhalogen-free
Goodresistancetooilsandweathering
ResistanttoUVradiationandozone
Coreidentification,seetablebelow
Nominalvoltage
upto1mm²=U
0
/U300/500V
from1,5mm²=U
0
/U450/750V
atfixedandprotectedinstallation
from1,5mm²=U
0
/U600/1000V
Resistanttosolderingtemperatures
Tests
ThermalclassB
Flametest(unitflametest)acc.to
DINVDE0482-332-3-22,BS4066Teil3,
DINEN60332-3-22,IEC60332-3-22
(previouslyDINVDE0472
part804testmethodC)
Thesesingle-corecablesareresistantto
melting,evenwhenincontactwitha
solderingironattemperaturesofbetween
300°Cand380°C,becauseofthe
cross-linkingfortheinsulationmaterial
Testvoltage
3500V
Flametest(cable)acc.to
DINVDE0482-332-1-2,DINEN60332-1-2,
IEC60332-1-2(equivalentDINVDE0472
part804testmethodB)
Minimumbendingradius
flexing12,5xcoreØ
fixedinstallation4xcoreØ
Duetothehightemperatureprofilethe
crosssectionofconductorcanundercertain
circumstancesbereduced,herebyenabling
asavinginspacerequirementandweight
Caloricloadvalues
see"TechnicalInformations"
Corrosivenessofcombustiongases
acc.toDINVDE0482part267,
DINEN50267-2-2,IEC60754-2
(equivalentDINVDE0472part813)
Thematerialsusedduringmanufacturing
arecadmium-free,containnosilicone
andarefreefromsubstancesharmful
tothewettingpropertiesoflacquers
Approval
GermanischerLloyd
Halogen-freeacc.toDINVDE0482part267,
DINEN50267-2-1,IEC60754-1
(equivalentDINVDE0472part815)
Smokedensityacc.toDINVDE0482
part1034-1+2,DINEN61034-1+2,
IEC61034-1+2,BS7622part1+2
(previouslyDINVDE0472part816)
Application
Thesetemperatureresistantsingle-corecablesareusedfortheinternalwiringoflightingfixtures,heaters,electricalmachinery,switchingsystems
anddistributorsinequipmentandplantandmachinery,suitableforlayingintubesonandunderplaster,inclosedinstallationducts,aswellasfor
trafficsystemsandoutdoorapplications.Thesecablesarenotapprovedfordirectroutingonracks,guttersortanks.Thesehalogen-freesinglecore
cablesarecharacterisedbytheiramazinglyhighlong-timeresistancetotemperatureandfeatureamongtheleadinghalogen-free,flameresistant
productsintheworld.Thesesinglecorecablessignificantlycontributetosafetyandtheenvironment.
=ProductconformswithLow-VoltageDirective2014/35/EU.
Weight
app.
kg/km
Cop.
weight
kg/km
OuterØ
app.mm
Cross-
sec.
mm²
2-col.BEIGEOGD-BUGNYEVTGYWHRDBNBUGN-YEBK
5116551164510775107951078510765107551074510735107251071510705099850999Partno.
4,02,41,60,25
5117951178511755117751176511745117351172511715117051169511685116651167Partno.
5,03,21,70,34
5129351292512895129151290512885128751286512855128451283512825128051281Partno.
7,04,81,90,5
5130751306513035130551304513025130151300512995129851297512965129451295Partno.
11,07,22,20,75
5132151320513175131951318513165131551314513135131251311513105130851309Partno.
14,09,62,51
5133551334513315133351332513305132951328513275132651325513245132251323Partno.
20,014,42,91,5
5134951348513455134751346513445134351342513415134051339513385133651337Partno.
30,024,03,52,5
5136351362513595136151360513585135751356513555135451353513525135051351Partno.
47,038,04,34
5137751376513735137551374513725137151370513695136851367513665136451365Partno.
72,058,05,06
5139151390513875138951388513865138551384513835138251381513805137851379Partno.
120,096,06,310
Continuation
27.09.2016/Dimensionsandspecificationsmaybechangedwithoutpriornotice.

Summary of content (2 pages)