Installation, Use and Care Manual

4. IF THE HOOD IS TO BE “BACK VENTED”, PROCEED DIRECTLY TO STEP 5.
Consult the connection diagrams (following) for further details on exhaust outlet placement.
Method 1: Install the duct(s) from the outside of the home down to the location of the exhaust
outlet(s) on the top of the hood or to the transition (if applicable).
If a transition is used, install duct down to the location of the transition outlet plus 1”
[2.5 cm]. This will allow the transition to engage 1” [2.5 cm] inside of duct.
Method 2: Install the duct(s) from the outside of the home to the ceiling over the exhaust
outlet(s) on the hood. The end of the duct(s) should extend 1” [2.5 cm] below the
ceiling.
Use foil HVAC tape (not grey cloth duct tape) to seal all joints. See “VENT ACCESSORIES” on
page19 for a listing of available Hestan ducting materials.
TRANSITION HEIGHTS:TRANSITION HEIGHTS:
Single and Dual Blower (WM1L + WM2L = 900 CFM): 6” round duct will connect directly to
the top of the hood; 8” round will connect directly to the top of the hood. If using
the optional multi-blower transition (AKVT6810, sold seperately), a 10” round duct
connects to it 17-1/2” above top of hood. See “VENT ACCESSORIES” on page19 for
details.
Two Dual Blowers (Two WM2Ls = 1200 CFM): Two 8” round ducts connect directly to the
top of the hood. If using the optional multi-blower transition (AKVT8812, sold
seperately), a 12” round duct connects to it 16-1/2” above top of hood. See “VENT
ACCESSORIES” on page19 for details.
CONNECTION DIAGRAMS CONNECTION DIAGRAMS
8" Round
(Top View)
(Wall Side)
Centerline
of hood
Electrical (2)
Motor
Cooling
Vent (3)
6" [15.2 cm]
Round
7-5/16"
[18.6 cm]
1-7/8"
[4.8 cm]
5-1/4"
[13.3 cm]
1-3/4"
[4.4 cm]
7-5/16"
[18.6 cm]
5-1/2"
[14 cm]
Electrical (2
)
(Top view)
(Wall Side)
Centerline
of Hood
Motor
Cooling
Vent (4)
8" [20.3 cm]
Round
5-1/2"
[14 cm]
1-3/4"
[4.4 cm]
5-1/4"
[13.3 cm]
11"
[29.9 cm]
11"
[29.9 cm]
8" [20.3 cm]
Round
INSTALLATION
(CONT.)
©2020 Hestan Commercial Corporation
13