Installation Manual

EN
©2020 Hestan Commercial Corporation
11
LOCATION AND INSTALLATION/VENTILATION
(CONTINUED)
RECOMMENDED
GAS SHUT-OFF
VALVE LOCATION
G
ELECTRICAL
SUPPLY
LOCATION
FINISHED
FLOOR
E
COMBUSTIBLE
MATERIALS
MIN. CLEARANCE
TO NEAREST
COMBUSTIBLE
SIDE SURFACE
W
V
DIMENSIONS IN
BRACKETS [ ] ARE
IN CM.
COUNTERTOP
FULL OVERLAY
DRAWER FACE
FULL OVERLAY
CABINET DOOR FACE
1
8
"
[3.2 mm]
INSTALLATION CLEARANCES 30” WITH ISLAND TRIM
FRONT VIEW
1-1/2"
[3.8]
4"
[10.2]
11"
[27.9]
2-1/2"
[6.4]
7"
[17.8]
18"
[45.7]
12"
[30.5]
NOTES:
SHADED AREAS INDICATE WHERE COMBUSTIBLE MATERIALS ARE NOT ALLOWED.
APPLIANCE TOP MUST BE LEVEL OR HIGHER THAN THE ADJACENT COUNTERTOP SURFACES.
“G” IS GAS CONNECTION ZONE ON REAR WALL. MOUNT SHUT-OFF VALVE AS HIGH AS POSSIBLE IN THIS
ZONE FOR EASY ACCESS WHEN RANGE IS INSTALLED.
“E” IS ELECTRICAL SUPPLY ZONE.
“W” IS APPLIANCE OPENING.
NOTE: HANDLE END CAPS PROTRUDE 1/8” BEYOND EACH SIDE OF THE RANGE. ALLOWANCE MAY BE
NEEDED FOR ADJACENT DRAWERS OR CABINETRY.
“V” IS MIN. CLEARANCE TO REQUIRED VENTILATION HOOD.
RANGE MODEL
W
V (MIN)
KRD304 30” [76.2] 30” [76.2]