LOCATION AND INSTALLATION/VENTILATION
(CONTINUED)
COMBUSTIBLE
MATERIALS
36-7/8 - 38-3/8”
[93.6 - 97.5]
TO COOKING
SURFACE
48-5/16”
[122.7]
61/31-03
[78.3]
61/11-42
[62.7]
13” [33]
MAX.
3”
[7.6]
LOW
BACKGUARD
MAX.
RECESS
DEPTH
APPLIANCE
TOP
COOKING
SURFACE
SIDE VIEW
LOCATION OF GAS AND
ELECTRICAL ON FLOOR
W
3”
[7.6]
V
12”
[30.5]
6”
[15.2]
VENT HOOD
COMBUSTIBLE
MATERIALS
18” [45.7]
MIN.
FRONT VIEW
DIMENSIONS IN
BRACKETS [ ]
ARE IN CM.
MIN. CLEARANCE
TO NEAREST
COMBUSTIBLE
SIDE SURFACE
FINISHED
FLOOR
INSTALLATION CLEARANCES WITH LOW BACKGUARD
11”
[28]
18”
[45.7]
G
11”
[28]
RECOMMENDED
GAS SHUT-OFF
VALVE LOCATION
ELECTRICAL
SUPPLY
LOCATION
5”
[12.7]
E
2-1/2”
[6.4]
LEVELING
The range must be level, especially those models featuring a griddle. Raise or lower the range to the
desired height by adjusting the four leveling legs under the range. The legs can be turned by hand. It
may be necessary to use a lever or other lifting device to assist in
temporarily raising the unit to turn the legs. Do not lift or lever
from the front or back, only from the sides.
The appliance top must be level or
higher than the adjacent countertop
surfaces. Failure to adjust the height
may expose the adjacent cabinets to excessive heat which may
damage the cabinets or countertop.
REF 1.12”
[2.84 cm]
CAUTION
RANGE MODEL
W V (MIN)
KRG365 36” [91.4] 30” [76.2]
KRG364GD 36” [91.4] 30” [76.2]
NOTES:
*
SHADED AREAS INDICATE WHERE COMBUSTIBLE
MATERIALS ARE NOT ALLOWED.
*
APPLIANCE TOP MUST BE LEVEL OR HIGHER
THAN THE ADJACENT COUNTERTOP SURFACES.
*
"G" IS GAS CONNECTION ZONE ON REAR WALL. MOUNT SHUT-OFF VALVE AS HIGH AS
POSSIBLE
IN THIS ZONE FOR EASY ACCESS WHEN RANGE IS INSTALLED.
*
"E" IS ELECTRICAL SUPPLY ZONE.
*
"W" IS APPLIANCE OPENING.
*
"V" IS MIN. CLEARANCE TO REQUIRED VENTILATION HOOD.