DRC Valve Controller  
DRCx-xxx - The title parameter is fixed. It displays the model number and the firmware version. 
Cx MODE - Three modes of operation. 
Mode 
Enable 
Channels and description 
1 IN1 NO ENBL 
1, 2, 3, 4, use its own input. 
2 IN1 USE ENBL 
x 
1, 2, 3, 4, use its own input. 
3 IN1 FOLLOWER 
2 (use input from C1), 4 (use input from C3) 
E.g., to drive two-coil directional proportional valve(s), set C1 & C3 to mode 1 or mode 2, Set C2 & C4 to 
mode 3. Do not overlap the input ranges. 
Cx MIN INPUT - Sets the minimum command input. The input can be inverted. The value in the brackets is the 
present command input. This parameter is a combination variable/monitor type. 
Cx MAX INPUT - Sets the maximum command input. The input can be inverted. The value in the brackets is the 
present command input. This parameter is a combination variable/monitor type. 
Cx  MIN  OUTPUT  -  Sets  the minimum  output current  (milliamps  for  -06A,  amps  for  -12A,-25A).  It  cannot be 
inverted.  The  value  in  the  brackets  is  the  present  output  current.  This  parameter  is  a  combination 
variable/monitor type. 
Cx MAX OUTPUT - Sets the maximum output current (milliamps for -06A, amps for -12A,-25A). The value in the 
brackets is the present output current. This parameter is a combination variable/monitor type. 
Cx RAMP UP/DOWN - Sets the time for output current to ramp Up or Down through the full input range. These 
parameters are variable. 
DITHER FREQ.  Options: 30, 50, 75, 100, 125, 150, 175, 200, 225, 250, 275, 300, and 1000 Hz. Set the PWM or 
dither frequency according to the valve specifications. This parameter is variable. 
Cx COMMAND INPUT - Displays the present input. This parameter is a monitor type. 
Cx OUTPUT CURRENT - Displays the present output current. This parameter is a monitor type. 
SUPPLY VOLTAGE - Displays the  is helpful for troubleshooting. This parameter 
is a monitor type. 
FAULT STATUS - The STATUS LED will flash red 2 times for Coil Open and 3 times for Coil Short. 