DRC Valve Controller  
Open Loop Double Solenoid Control (DRC2-Vxx) 
The DRC can drive a double solenoid valve with a 
joystick or potentiometer of . 
If enable switch is not used, set channel 1 to be Mode 
1, channel 2 to be Mode 3. 
If enable switch is used, set channel 1 to be Mode 2, 
channel 2 to be Mode 3. 
The minimum and maximum input parameters for the 
two channels should not be overlap.  
Set the dither and output settings according to the 
valve specifications. 
Schematic  
FUSE
+V Power Input
 9 - 32VDC
+V = Enabled
PWR J1-1 
DRC2
Electronic Valve
Controller
Enable J1-3
GND J1-2
-10V Ref. Out J4-1
+10VDC @ 20mA
0 to 10VDC
+10V Ref. Out J4-3
Ch. 1 I/P J5-1
Sig GND J4-2
J5-2
VDC I/P
mA I/P
Supply Voltage
4-20mA
Ch. 2 I/P J5-3
Prop. PWM (Sourcing)
Sig GND J2-2
Ch. 1 Out J2-1
Ch. 2 Out J2-3
Prop. PWM (Sourcing)
0 to -10VDC
Example Settings 
Input / Output Diagram 
-10V
(Ch. #2)
600mA
5mA
600mA
5mA
Center (0V)
Ch. #2
Current
Ch. #1 
Current
10V
(Ch. #1)
Command 
Input
-0.2V 
(Ch. #2)
0.2V 
(Ch. #1)
Parameter 
Value 
C1 Mode 
2 IN1 USE ENBL 
C1 Min input 
0.2 V 
C1 Max input 
10.0 V 
C1 Min output 
5 mA 
C1 Max output 
600 mA 
C1 Ramp up 
1 S 
C1 Ramp down 
1 S 
C2 Mode 
3 IN1 FOLLOWER 
C2 Min input 
-0.2 V 
C2 Max input 
-10.0 V 
C2 Min output 
5 mA 
C2 Max output 
600 mA 
C2 Ramp up 
0 S (NOT USED) 
C2 Ramp down 
0 S (NOT USED) 
Dither frequency 
150 Hz. 