User guide
P/N: 021-00154, Rev. A.6 - updated for V4.7 Tools     Page | 152  
Our DVC products have an available computer interface to your PC. This is by far the most effective way to 
setup and troubleshoot our products. We provide all of the information represented by the LEDs plus a lot more. 
Meters and running graphs give quick looks at what your system is doing, while enunciators tell you what the 
unit is trying to do. Data logging and remote operation can be used to consult with our staff to help debug 
difficult problems. 
Troubleshooting the CAN Bus Communication network 
Once the uni
t is correctly wired and known to be functioning as HCT intended, the machine may still not be 
functioning as you intended. The most common problem is communication settings. Flashing NS or MS LEDs 
on DVC modules indicates problems. Three common causes of network NS problems are lack of or a loose bus 
terminator component, inconsistent baud rates across the set of connected DVC modules and incorrect MAC ID 
settings on 1 or more modules. The module baud rates and MAC IDs can be determined by connecting a 
RS232 cable between your PC running the Program Loader Monitor and the DVC unit. The settings should 
agree with the setting programmed in the DVC10.   
Good grounding practices 
When welding on the machine, all power and ground connections need to be removed from the controller. Be 
aware, that some sensor manufactures ground their switch cases. If a switch case is grounded, such as a 
pressure transducer, then that ground could be connected to the DVC module and therefore compromise the 
integrity of the controller during welding. 
Ground the controller on all pins using suitable grounding wire. 