Coil A/B Min Current (0 to 2.5Amps) 
  Determines the min current or duty cycle. Fine tune this value to balance machine safety and valve 
responsiveness. Typical values for th 
Coil A/B Max Current (0 to 3Amps) 
  ONax output current. Typical values can be found in the valve 
 
OFF, the Coil A/B Min Current setting does not apply and is grayed out. The Max 
Current is used as an internal reference to declare a coil short condition when the output current is 0.5A higher 
than the max current setting. 
OFFhe output PWM duty cycle (0-100%) matches the percent of demand. The 
current will change when supply voltage and/or coil temperature changes. 
In this example, the output PWM duty cycle 
(0-100%) matches the percent of demand. 
The output current will change when supply 
voltage and/or coil temperature changes. 
The evc/epc does not declare an error 
because the output current 1.16A is not 
0.5A higher than the max setting 0.7A. 
In this example, the evc/epc declared an 
error because the output current 1.16A is 
0.5A higher than the max setting 0.63A. 