023-00354-Rev1.6 evc/epc User Manual 18
Copyright © High Country Tek, Inc. 2013
evc/epc Controller
With SAE J1939 Interface
Coil A/B Min Current (0 to 2.5Amps)
Determines the min current or duty cycle. Fine tune this value to balance machine safety and valve
responsiveness. Typical values for th
Coil A/B Max Current (0 to 3Amps)
ONax output current. Typical values can be found in the valve

OFF, the Coil A/B Min Current setting does not apply and is grayed out. The Max
Current is used as an internal reference to declare a coil short condition when the output current is 0.5A higher
than the max current setting.
OFFhe output PWM duty cycle (0-100%) matches the percent of demand. The
current will change when supply voltage and/or coil temperature changes.
In this example, the output PWM duty cycle
(0-100%) matches the percent of demand.
The output current will change when supply
voltage and/or coil temperature changes.
The evc/epc does not declare an error
because the output current 1.16A is not
0.5A higher than the max setting 0.7A.
In this example, the evc/epc declared an
error because the output current 1.16A is
0.5A higher than the max setting 0.63A.