evc/epc Controller  
With SAE J1939 Interface 
Pulse/AIN 2 Settings 
Pulse Input Selections (Analog or Pulse)  Select 
analog to use this input as analog input 2 for dual 
valve control or select pulse to use this input as the 
pulse input for anti-stall function. 
0-5V, 0-10V & ±1V (Enabled/OFF)  Select the 
voltage range that matches the analog input signal. 
The ±1V only applied to Pulse input. 
For anti-stall function, match the voltage range to 
the Pulse Pick UP. The signal can be 0-5VDC, or 
0-10VDC, or ±1VDC. 
Pulses per revolution PPR - (1 to 65535)  Enter 
the pulse per revolution of the speed sensor. 
Maximum displayed RPM (1 to 65535)  Visual only - scales the RPM gauge on the Dashboard. 
Keep this value near the maximum RPM to assure the resolution and accuracy. 
RPM slow Set-Point or Max Load RPM (1 to 65535)  The set-point where coil A current starts to reduce in Anti-
Stall or HP limit modes. 
RPM stop Set-Point or No Load RPM (1 to 65535)  The set-point where coil A current reaches 0 in Anti-Stall or 
HP limit modes. If auto-reverse is ON, reverse cycle will start at this rpm.