MVP-SVR Power Saver Valve Controller  
Parameter List 
The following table outlines the MVP-SVR parameters as well as the limits and units of measure for each 
parameter. 
Parameter 
Limits 
Units 
MVP-SVR-xxx 
Version # 
Start time 
0.0 to 6.0 
Seconds 
Start current 
0 to 600
*
mA 
Hold current 
0 to 600
*
mA 
Output current 
mA 
Supply voltage 
Volts 
Fault status 
Fault 
*
0 to 1.2A for 12A version, 0 to 2.5A for 25A version 
MVP-SVR-xxx - The title parameter is fixed. It displays the model number and the firmware version. 
START TIME - Sets the amount of time the controller will operate at the Start Current after initial power up. It is 
typically very short, allowing only enough time for the valve spool to fully shift. 
START CURRENT - Sets the current to the valve during the Start Time after initial power up. This is the max valve 
current. The unit is in milliamps (amps for -12A,-25A). 
HOLD CURRENT - Sets the current to the valve after the Start Time has expired. It is a percentage of the max 
valve current. Always have a margin of error to ensure the valve stays in its on position when activated. The 
unit is in milliamps (amps for -12A,-25A). 
OUTPUT CURRENT - Displays the present output current. This parameter is a monitor type. 
SUPPLY VOLTAGE - Displays the  is helpful for troubleshooting. This parameter 
is a monitor type. 
FAULT STATUS - The STATUS LED will flash red 2 times for Coil Open and 3 times for Coil Short. 