Temperature Range
Select the temperature measurement range.
Version
View the version of current algorithm.
4. Click Save.
3.3.2 Set Normal Mode
This
funcon is used to measure the temperature of the whole scene and alarm.
Steps
1. Go to
Conguraon → Temperature Measurement → Basic Sengs , and check Enable
Temperature Measurement.
2. Refer to Set Thermography Parameters to set the parameters.
3. Go to
Conguraon → Temperature Measurement → Advanced Sengs , and select Normal.
4. Congure the parameters of normal mode.
Emissivity
Set the emissivity of your target. The emissivity of each object is
dierent.
Distance
The distance between the target and the device.
Pre-Alarm Threshold
When the temperature of target exceeds the pre-alarm threshold, and this status keeps more
than Filtering Time, it triggers pre-alarm.
Alarm Threshold
When the temperature of target exceeds the alarm threshold, and this status keeps more
than Filtering Time, it triggers alarm.
Pre-Alarm Output and Alarm Output
Check Pre-Alarm Output and Alarm Output to link the pre-alarm or alarm with the
connected alarm device.
5. Refer to Set Arming Schedule for
seng scheduled me. Refer to Linkage Method Sengs for
seng linkage method.
6. Click Save.
The maximum and minimum temperature will be displayed on the live view.
Note
Go to Image → VCA Rules Display to adjust the fonts size and the temperature colour of
normal, alarm and pre-alarm.