panel. Save current scene as certain preset.
You can set the preset in live view interface before and call the preset in the
temperature measurement and alarm interface.
You can set/ call/ clear the preset in temperature measurement interface.
Click Synchronize FOV this button to synchronize the FOV of thermal light
channel and optical light channel.
4. Configure the parameters.
1) Set the alarm rule: Select a temperature measurement rule from the rule list and
configure the parameters.
Name: You can customize the rule name.
Type: Select Point, Line, or Area as rule type.
Emissivity: Set the emissivity of your target. The emissivity of each object is
different, you can refer to the Quick Start Guide Appendix for details.
Distance (m): The straight-line distance between the target and the device.
Reflective Temperature: If there is any target with high emissivity in the scene,
check the checkbox and set the reflective temperature to correct the
temperature. If no such target exists, uncheck the checkbox.
Tolerance Temperature: The device judges whether the triggered alarm stops
until the device temperature/temperature difference is lower than rule
temperature by tolerance temperature. E.g., set tolerance temperature as C,
set alarm temperature as 55° C, and set pre-alarm temperature as 50° C. The
device sends pre-alarm when its temperature reaches 50° C and it alarms when
its temperature reaches 55° C and only when the device temperature is lower
than 52°C will the alarm be cancelled.
2) Set the alarm rules.
For Point Rule:
a) Click to show the Alarm Rule setting interface.
Figure 5-28 Alarm Rule Settings (Point)
b) Set the alarm rule.