User Manual

Network Video Recorder User Manual
UM NVR v4.xx 111717NA 119
Figure 12-7 One-Key Alarm Disarming
Step 6 Select the alarm linkage action(s) you want to disarm for the local Alarm Input .
When Alarm Input 1 (Local < -1) is enabled with one-key disarming, the other
alarm input settings are not configurable.
Step 7 Click Apply to save the settings.
12.6.3 Configuring Alarm Outputs
Trigger an alarm output when an alarm is triggered.
Step 1 Go to System > Event > Normal Event > Alarm Output.
Step 2 Select an alarm output item from the list and click .
Step 3 Edit the alarm name.
Step 4 Select the dwell time (the alarm duration) from 5s to 600s, or Manually Clear.
Step 5 Manually Clear: You should manually clear the alarm when the alarm occurs.
Refer to Chapter 12.9 Triggering or Clearing Alarm Output Manually for detailed
instructions.
Step 6 Set the arming schedule. Refer to Chapter 12.1 Configuring Arming Schedule.