Quick Start Guide

Access Control Terminal·Quick Start Guide
18
When the access control terminal works as a card reader, you must the WG_ERR, BUZZER and
WG_OK interfaces if you want to control the LED and buzzer of the Wiegand card reader.
Set the working mode of the terminal as card reader, which can be configured in System
Parameter > Mode Switch, if the terminal is required to work as a card reader. The card
reader mode support to communicate by Wiegand or RS-485.
The distance of Wiegand communication should be no longer than 80 m.
The external power supply and the access control terminal should use the same GND cable.
The Wiring of RS-485 Output 5.7.2
Figure 5-10 Access Control Terminal RS-485 Connection Diagram
Set the working mode of the terminal as card reader, which can be configured in System
Parameter > Mode Switch, if the terminal requires working as a card reader.
When the access control terminal works as a RS-485 card reader, the default RS-485 address is
1. RS-485 address can also be configured in System Parameter -> Serial Port Settings.
The external power supply and the access control terminal should use the same GND cable.