Configuration Manual

Steps
1.
Click Access Control and Elevator to enter corresponding conguraon page.
Figure 1-16 Access Control and Elevator
2.
Set the Access Control parameters.
1) Select the door No.
2) Set the Door-unlocked Duraon.
3)
Oponal: Enable Upload Alarm for Not-Closed Door.
4) Click Save to enable the sengs.
Note
The door-unlocked duraon ranges from 1 s to 255 s.
If you check Upload Alarm for Not-Closed Door, an alarm will be triggered
automacally if the door is not locked in the congured duraon.
Enabling Card Encrypt, the door staon can recognize the encrypted
informaon of the card when you swiping the card on the door staon.
3.
Set the Elevator Control parameters.
1) Select an elevator No., and select an elevator controller type for the elevator.
2) Set the
negave oor.
Module Door
Staon Conguraon Guide
12