TABLE 3—ALLOWABLE LOADS FOR HILTI ROD AND WIRE HANGER ASSEMBLIES INSTALLED INTO SAND-LIGHTWEIGHT
CONCRETE AND COMPOSITE STEEL DECK PANELS
1,2,3,4,5,6,7,9
HANGER
ASSEMBLY
ALLOWABLE LOADS (lbf)
Fastener
Location:
Installed into
Structural Sand-
lightweight Concrete
Installed through 1
1
/
2
in. Deep Steel Deck Panel
Into Sand-lightweight Concrete
Installed through 3 in. Deep Steel Deck Panel Into
Sand-lightweight Concrete
Upper Flute
Lower Flute
Upper Flute
Lower Flute
Load Direction: Tension
Shear
45-
degree
Tension
Shear
45-
degree
Tension
Shear
45-
degree
Tension
Shear
45-
degree
Tension
Shear
45-
degree
X-DR ALH22
–
–
–
–
–
–
–
–
–
100
(10)
–
–
40
(10)
–
–
X-DR ALH27
–
–
–
–
–
–
–
–
–
100
(10)
–
–
80
(10)
–
–
X-DR MX
installed with an
X-P 20 B3
fastener
– – – – – – – – – 80
(10)
– – 60
(10)
– –
X-MW ALH22
–
–
–
–
–
–
–
–
–
100
–
100
90
–
100
X-MW ALH27
–
–
–
–
–
–
–
–
–
100
–
100
100
–
100
X-MW ALH32
–
–
–
–
–
–
–
–
–
100
–
100
100
–
100
X-MW MX
installed with an
X-P 20 B3
fastener
– – – – – – – – – 80
(10)
– – 60
(10)
– –
X-HS U32
95
115
105
8
95
220
135
8
95
220
135
8
125
220
175
8
95
220
135
8
For SI: 1 inch = 25.4 mm, 1 lbf = 4.4 N, 1 psi = 6895 Pa.
1
Fasteners must not be driven until the concrete has reached the specified compressive strength.
2
Concrete material thickness at the point of penetration must be a minimum of 3 inches, except as shown in Figures 10 through 13.
3
Deck panel must have a minimum No. 20 gage (0.0359 inch) base-metal thickness and a minimum yield strength of 33,000 psi.
4
Nailhead Standoff, h
NVS
, must be less than or equal to
1
/
4
inch for the X-DR, less than or equal to
5
/
16
inch for the X-MW ALH assemblies, less than or equal to
3
/
16
inch
for the X-DR MX and X-MW MX assemblies, less than or equal to
3
/
8
inch for the X-HS U32 hanger assembly and as indicated in the Hilti installation instructions. See
Figures 6, 7 and 8, as applicable.
5
Allowable loads apply to X-HS threaded rod hanger assemblies with either the
1
/
4
- or
3
/
8
-inch-diameter internally threaded hole.
6
See Figures 9a, 9b and 9c for load directions for the X-HS assemblies.
7
See Figures 10 through 13 for nominal flute dimensions, fastener locations, and load orientations.
8
Allowable loads for 45-degree applications are based on testing. For allowable loads at other angles of installation, refer to Section 4.1.2.
9
Allowable loads are for concrete with minimum f′
c
of 3,000 psi, unless otherwise noted.
10
Allowable loads are for concrete with minimum f′
c
of 3,500 psi.
TABLE 4—X-MW ALH WIRE HANGER ASSEMBLY VARIATIONS
CLIP ASSEMBLY NUMBER
FASTENER
WIRE LENGTH [feet (m)]
X-MW ALH22
X-ALH-22
10 (3)
X-MW ALH27 X-ALH-27
6 (2)
10 (3)
20 (6)
X-MW ALH32
X-ALH-32
10 (3)
FIGURE 1 – X-DR ROD HANGER ASSEMBLY
FIGURE 2 – X-DR MX ROD HANGER ASSEMBLY