ICC ESR-1545 for HSL-3 Heavy Duty Expansion Anchors

ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be
construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or
implied, as to any finding or other matter in this report, or as to any product covered by the report.
Copyright © 2021 ICC Evaluation Service, LLC. All rights reserved. Page 13 of 14
ICC-ES Evaluation Report
ESR-1545 LABC and LARC Supplement
Reissued March 2020
Revised March 2021
This report is subject to renewal March 2022.
www.icc-es.org | (800) 423-6587 | (562) 699-0543 A Subsidiary of the International Code Council
®
DIVISION: 03 00 00—CONCRETE
Section: 03 16 00—Concrete Anchors
DIVISION: 05 00 00—METALS
Section: 05 05 19—Post-Installed Concrete Anchors
REPORT HOLDER:
HILTI, INC.
EVALUATION SUBJECT:
HILTI HSL-3 CARBON STEEL AND HSL-3-R STAINLESS STEEL HEAVY DUTY EXPANSION ANCHORS FOR
CRACKED AND UNCRACKED CONCRETE
1.0 REPORT PURPOSE AND SCOPE
Purpose:
The purpose of this evaluation report supplement is to indicate that the Hilti HSL-3 carbon steel and HSL-3-R stainless steel
heavy duty expansion anchors in cracked and uncracked concrete, described in ICC-ES evaluation report ESR-1545, have
also been evaluated for compliance with the codes noted below as adopted by the Los Angeles Department of Building and
Safety (LADBS).
Applicable code editions:
2020 City of Los Angeles Building Code (LABC)
2020 City of Los Angeles Residential Code (LARC)
2.0 CONCLUSIONS
The Hilti HSL-3 carbon steel and HSL-3-R stainless steel heavy duty expansion anchors, described in Sections 2.0 through
7.0 of the evaluation report ESR-1545, comply with LABC Chapter 19, and LARC, and are subjected to the conditions of use
described in this supplement.
3.0 CONDITIONS OF USE
The Hilti HSL-3 carbon steel and HSL-3-R stainless steel heavy duty expansion anchors described in this evaluation report
supplement must comply with all of the following conditions:
All applicable sections in the evaluation report ESR-1545.
The design, installation, conditions of use and identification of the anchors are in accordance with the 2018 International
Building Code
®
(2018 IBC) provisions noted in the evaluation report ESR-1545.
The design, installation and inspection are in accordance with additional requirements of LABC Chapters 16 and 17, as
applicable.
Under the LARC, an engineered design in accordance with LARC Section R301.1.3 must be submitted.
The allowable and strength design values listed in the evaluation report and tables are for the connection of the anchors
to the concrete. The connection between the anchors and the connected members shall be checked for capacity (which
may govern).
For the design of wall anchorage assemblies to flexible diaphragms, the anchor shall be designed per the requirements of
City of Los Angeles Information Bulletin P/BC 2020-071
This supplement expires concurrently with the evaluation report, reissued March 2020 and revised March 2021.