Not to be distributed outside of FM Global except by Customer APPROVAL REPORT APPROVAL OF HILTI CABLE TRANSIT SYSTEM CFS-T FOR USE IN WALL AND FLOOR ASSEMBLIES RATED UP TO AND INCLUDING 2 HOURS Prepared for: HILTI, INC. 5400 SOUTH 122ND EAST AVENUE TULSA, OK 74146 Project ID: 3046888 Class: 4990 Date of Approval: 1/16/2013 Authorized by: Cynthia E. Frank, Group Manager Assistant Vice President FM Approvals 1151 Boston-Providence Turnpike P.O.
FM APPROVALS Project ID: 3046888 APPROVAL OF HILTI CABLE TRANSIT SYSTEM CFS-T FOR USE IN WALL AND FLOOR ASSEMBLIES RATED UP TO AND INCLUDING 2 HOURS for HILTI, INC. 5400 SOUTH 122ND EAST AVENUE TULSA, OK 74146 I INTRODUCTION 1.1 Hilti, Inc. submitted their Cable Transit System CFS-T devices for examination to determine if they meet the FM Approvals requirements of the Standard listed below when installed in fire rated gypsum walls and concrete floor or wall assemblies.
FM APPROVALS Project ID: 3046888 II MATERIAL DESCRIPTIONS 2.1 The Hilti Cable Transit System, Model CFS-T, is a system used to firestop openings in rated floors and walls. The units are designed principally for the shipping and offshore industries. The units are either rectangular or round in shape. The devices examined in the program consist principally of a galvanized steel frame, elastomeric sealing modules, steel anchor and a steel compression device with adjusting nut.
FM APPROVALS Project ID: 3046888 3.2 Approval Standard 4990 requires that all through penetrations shall be subjected to a fire resistance test conducted in accordance with ASTM E814 (08) "Standard Method for Fire Tests of Through-Penetrations Fire Stops” followed by a hose stream test conducted in accordance with ASTM E2226 (07), “Practice for Application of Hose Stream”. An hourly rating will be assigned based on the time period for which it successfully met the performance criteria. 3.
FM APPROVALS Project ID: 3046888 IV TEST ASSEMBLIES 4.1 This test program consisted of two (2) wall assemblies and one (1) floor assembly. The wall assemblies incorporated two (2) openings while the floor assembly incorporated three (3) openings. A description of the test assembly is given below. 4.1.1 Test Specimen No. 1 (Ref. TBTL 908a) consisted of a 2 hour fire rated gypsum wall with steel studs. The wall contained two (2) separate openings as described below.
FM APPROVALS Project ID: 3046888 4.1.3 Test Specimen No. 3 (Ref. TBTL 909a) consisted of a 2 hour fire rated gypsum wall with steel studs. The test specimen was identical to Test Specimen No. 1. When installed within a wall, the units are not symmetrical. One side of the wall contains the unit while the other side of the wall contains mineral wool. Since it could not be determined which side would be more critical, separate fire tests had to be conducted exposing each side of the wall to the fire.
FM APPROVALS Project ID: 3046888 5.
FM APPROVALS Project ID: 3046888 VII MANUFACTURER'S RESPONSIBILITIES 7.1 Approval is based upon the fabrication of the fire stop assemblies in accordance with this Approval Report, satisfactory field experience, and continued use of acceptable quality control procedures as determined by Facilities and Procedures Audits. 7.
FM APPROVALS Project ID: 3046888 9.3 For the specific constructions, limitations and hourly rating see Appendices A – E, Fire Stop Design Nos. 666 - 670. 9.4 Continued Approval is contingent upon satisfactory field performance, production of products in accordance with this report and acceptable quality control procedures as determined by follow-up Facilities and Procedures Audits. 9.
FM APPROVALS 3046888 Appendix A Page 1 of 2 FIRE STOP DESIGN 666 F Rating – 2 HR T Rating – ½ and ¾ HR (see Item 4) TFM Rating – ¾ HR 1. WALL ASSEMBLY. Two hour fire rated gypsum wall assembly consisting of steel channel studs. Gypsum Board. Min 5/8 in. (16 mm) thick x 4 ft (1.2 m) wide gypsum wallboard applied to each side of the wall.
FM APPROVALS 3046888 Page 2 of 2 3.FIRESTOP SYSTEM. The firestop system shall consist of the following: A. Rectangular Firestop Devices – Each firestop device consists of a rectangular steel frame, multidiameter elastomeric sealing modules, steel anchor plates and a wedge seal unit. The firestop device shall be inserted into the framed opening on one side of the wall assembly.
FM APPROVALS 3046888 Appendix B Page 1 of 2 FIRE STOP DESIGN 667 F Rating – 2 HR T Rating – ½ HR TFM Rating – ½ HR 1. WALL ASSEMBLY. Two hour fire rated gypsum wall assembly consisting of steel channel studs. Gypsum Board. Min 5/8 in. (16 mm) thick x 4 ft (1.2 m) wide gypsum wallboard applied to each side of the wall.
FM APPROVALS 3046888 Page 2 of 2 3.FIRESTOP SYSTEM. The firestop system shall consist of the following: Circular Firestop Devices – Circular firestop device for use in preformed openings. The firestop device shall be inserted into the framed opening and friction fit on one side of the wall assembly. Each device consists of a seal plug unit with compression device and single/multi-diameter elastomeric sealing modules.
FM APPROVALS 3046888 Appendix C Page 1 of 2 FIRE STOP DESIGN 668 F Rating – 2 HR T Rating – ¾ HR TFM Rating – ¾ HR and 1 HR (see item 3) 1. FLOOR OR WALL ASSEMBLY. Min 4-1/2 in. (114 mm) thick lightweight or normal weight concrete floor or wall, or minimum 8 in. (200 mm) thick concrete block wall. Max size of opening is 11.8 in. x 11.0 in. (300 mm x 280 mm). 2. FIRESTOP SYSTEM.
FM APPROVALS 3046888 Page 2 of 2 modules shall be left in place or “blank” (solid) sealing modules shall be used. During the installation of the elastomeric sealing modules, thin steel anchor plates shall be used to separate the rows of sealing modules and to retain the sealing modules within the steel frame. After installation of the modules, the bolts of the compression unit are tightened to form an effective seal around the penetrants and insert modules.
FM APPROVALS 3046888 Appendix D Page 1 of 2 FIRE STOP DESIGN 669 F Rating – 2 HR T Rating – ¾ HR and 1 HR (see item 3) TFM Rating – 1 HR 1. FLOOR OR WALL ASSEMBLY. Min 4-1/2 in. (114 mm) thick lightweight or normal weight concrete floor or wall, or minimum 8 in. (200 mm) thick concrete block wall. Max size of the opening is 11.8 in. x 5.5 in. (300 mm x 140 mm). 2. FIRESTOP SYSTEM.
FM APPROVALS 3046888 Page 2 of 2 each device frame shall be filled with multiple rows of multi-diameter elastomeric sealing modules with a max of one (1) cable per sealing module. When the number of sealing modules exceeds the number of cables, the solid cylindrical cores of the unpenetrated multi-diameter sealing modules shall be left in place or “blank” (solid) sealing modules shall be used.
FM APPROVALS 3046888 Appendix E Page 1 of 2 FIRE STOP DESIGN 670 F Rating – 2 HR T Rating – ½ HR and 1 HR (see item 3) TFM Rating – 1 HR 1. FLOOR OR WALL ASSEMBLY. Min 4-1/2 in. (114 mm) thick lightweight or normal weight concrete floor or wall, or minimum 8 in. (200 mm) thick concrete block wall. Max size of the opening is or 8.5 in. (215 mm) in diameter. 2.FIRESTOP SYSTEM.
FM APPROVALS 3046888 Page 2 of 2 nd Hilti Inc, 5400 S 122 East Ave, Tulsa, OK 74146 Cable Transit System CFS-T Frame and Sealing Modules – Types CFS-T RR-50 GS; CFS-T RR-75 GS; CFS-T RR-100 GS; CFS-T RR-125 GS; CFS-T RR-150 GS; CFS-T RR-200 GS; and corresponding flanges CFS-T SLF-50 GS; CFS-T SLF-75 GS; CFS-T SLF-100 GS; CFS-T SLF-125 GS; CFS-T SLF-150 GS and CFS-T SLF-200 GS 3. CABLES. Aggregate cross-sectional area of the cables in each device shall be from 0 to 100% fill.