Installation Typicals - Fastening on Steel Threaded Studs

APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMER
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
285 167 118 91 75 63 54 48
4.0
346 211 151 118 97 82 71 63
5.0
397 250 182 143 118 101 88 77
6.0
440 285 211 167 138 118 103 91
7.0
477 317 237 190 158 135 118 105
8.0
510 346 262 211 176 151 133 118
FASTENER OVERVIEW
x
2 studs
per strut
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
112 67 48 37 31 26 22 20
4.0
135 84 61 48 39 34 29 26
5.0
153 99 73 58 48 41 36 32
6.0
168 112 84 67 56 48 42 37
7.0
181 124 94 76 64 55 48 43
8.0
192 135 104 84 71 61 54 48
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
7.00 3.50 2.00 0.25
4.0
9.25 4.75 2.50 0.25
5.0
11.75 6.00 3.25 0.50
6.0
14.00 7.25 4.00 0.50
7.0
16.50 8.50 4.75 0.75
8.0
18.75 9.75 5.25 0.75
Application
Fastening of cable trays, pipes on a horizontal cantilever support, fastened on
a horizontal structure
Support is fastened by two X-BT-MF (horizontal distance x)
L1 is the distance of the load center to the vertical structure surface
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of X-BT-MF threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer 2018/05/04
Load F acting at the distance of L1 from structure surface
NOTE: load capacity used for calculation N
rec
= 340 lb (axial) / V
rec
= 500 lb (shear)
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and X-BT-MF distance x)
FASTENING STRUT TO STEEL
WITH X-BT-MF
Two X-BT-MF Threaded studs
X-BT-MF • Imperial
101Issued August 2018, expiry January 2022