Installation Typicals - Fastening on Steel Threaded Studs

APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMER
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEW
4 studs
2 studs
1 stud
x
x
2 studs
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
4.0
24.00 17.00 13.25 9.75 8.00 6.25 5.25 4.50
6.0
36.25 25.50 20.00 14.75 12.00 9.50 8.00 6.75
8.0
48.25 34.00 26.75 19.50 16.00 12.75 10.75 9.00
14.0
84.75 59.50 47.00 34.50 28.00 22.50 18.75 16.00
20.0
121.00 85.25 67.25 49.25 40.25 32.25 26.75 23.00
32.0
193.75 136.25 107.5 0 78.75 64.25 51.75 43.00 36.75
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
4.0
539 270 180 135
6.0
809 404 270 202 162 135
8.0
539 359 270 216 180 154 135
14.0
629 472 377 315 270 236
20.0
674 539 449 385 337
32.0
719 616 539
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
4.0
270 135 90 67
6.0
404 202 135 101
8.0
270 180 135
14.0
315 236
20.0
337
32.0
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
4.0
13.25 9.75 8.00 5.25 4.00
6.0
20.00 14.75 12.00 8.00 6.00
8.0
26.75 19.50 16.00 10.75 8.00
14.0
47.00 34.50 28.00 18.75 14.00
20.0
67. 25 49.25 40.25 26.75 20.00
32.0
107.50 78.75 64.25 43.00 32.25
Application
Fastening of cable trays, pipes on a horizontal, braced cantilever support,
fastened on a vertical structure
Support is fastened by three / six X-ST-GR on both support and brace
baseplate with distance x
L1 is the distance of the load center to the vertical structure surface, the angle
of the brace is 45°
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of X-ST-GR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer 2018/05/04
Shear load fully carried by one / two top X-ST-GR (worst-case)
Load F acting at the distance of L1 from structure surface
NOTE: load capacity used for calculation N
rec
= 405 lb (axial) / V
rec
= 405 lb (shear)
Technical assessment maximum of F (depending on load F or lever arm length L1 and baseplate distance x)
FASTENING BRACED CANTILEVER SUPPORT
WITH X-ST-GR
Two / Four X-ST-GR Threaded studs
X-ST-GR • Imperial
114Issued August 2018, expiry January 2022