Installation Typicals - Fastening on Steel Threaded Studs
APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMER
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEW
x
2 studs
per strut
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
135 81 58 45 37 31 27 24
4.0
162 101 73 58 47 40 35 31
5.0
184 119 88 70 58 49 43 38
6.0
202 135 101 81 67 58 50 45
7.0
218 149 113 91 77 66 58 51
8.0
231 162 124 101 85 73 65 58
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
9.00 5.00 3.00 1.00
4.0
12.00 6.75 4.00 1.25
5.0
15.00 8.25 5.00 1.50
6.0
18.25 10.00 6.00 2.00
7.0
21.25 11.75 7.00 2.25
8.0
24.25 13.50 8.00 2.75
Application
• Fastening of cable trays, pipes on a horizontal cantilever support, fastened on a
vertical structure
• Support is fastened by two X-ST-GR (horizontal distance x)
• L1 is the distance of the load center to the center of the fasteners
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of X-ST-GR threaded stud. Structural
analysis of support / structure is NOT in Hilti scope. See the detailed statements in
disclaimer — 2018/05/04
• Shear load fully carried by one X-ST-GR (worst-case)
• Load F acting at the distance of L1 from structure surface
NOTE: load capacity used for calculation N
rec
= 405 lb (axial) / V
rec
= 405 lb (shear)
Technical assessment — maximum of L1 and F (depending on load F or lever arm length L1 and X-ST-GR distance x)
FASTENING STRUT TO STEEL
WITH X-ST-GR
Two / Four X-ST-GR Threaded studs
X-ST-GR • Imperial