Installation Typicals - Fastening on Steel Threaded Studs
2 studs
4 studs
APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMER
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEW
x
x
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
91.00 58.50
4.0
121.25 78.25 56.50
5.0
151.75 97.75 70.75
6.0
182.00 117. 25 85.00
7.0
212.50 137.00 99.25 61.50
8.0
242.75 156.50 113.25 70.25
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
154 154 154 154 154 154 154 154
4.0
190 190 190 190 190 190 190 190
5.0
221 221 221 221 221 221 221 221
6.0
247 247 247 247 247 247 247 247
7.0
271 271 271 271 271 271 271 271
8.0
291 291 291 291 291 291 291 291
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
85 85 85 85 85 85 85 85
4.0
108 108 108 108 108 108 108 108
5.0
128 128 128 128 128 128 128 128
6.0
146 146 146 146 146 146 146 146
7.0
162 162 162 162 162 162 162 162
8.0
178 178 178 178 178 178 178 178
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
4.0
56.50
5.0
70.75
6.0
85.00
7.0
99.25 61.50
8.0
113.25 70.25
Application
• Fastening of cable trays, pipes on a T-Post support, which is fastened on a
horizontal structure
• Support is fastened by two / four X-ST-GR (horizontal distance x)
• L1 is the total width of the T-Post, L2 is fix set to 1000 mm
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of X-ST-GR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
• 2 Load cases: load asymmetric acting in the center of one arm only,
30% acting as horizontal load
NOTE: load capacity used for calculation N
rec
= 405 lb (axial) / V
rec
= 405 lb (shear)
Technical assessment — maximum of L1 and F (depending on load F or lever arm length L1 and X-ST-GR distance x)
FASTENING T-POST (CEILING) SUPPORT
WITH X-ST-GR
Two / Four X-ST-GR Threaded studs
X-ST-GR • Imperial
117Issued August 2018, expiry January 2022