NOTE: load capacity used for calculation N
rec
= 3.6 kN (axial) / V
rec
= 4.3 kN (shear)
x
x
Application
• Fastening of cable trays, pipes on a horizontal, braced cantilever support,
fastened on a vertical structure
• Support is fastened by three / six X-BT-MR on both support and brace
baseplate with distance x
• L1 is the distance of the load center to the vertical structure surface, the angle
of the brace is 45°
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of X-BT-MR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
• Shear load fully carried by one / two top X-BT-MR (worst-case)
• Load F acting at the distance of L1 from structure surface
FASTENER TECHNICAL DETAILS
2 studs
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
100
585 500 390 325 280
150
880 750 585 485 420
200
1175 1000 780 650 560
350
2060 1755 1370 1140 985
500
2945 2505 1955 1630 1410
800
4715 4010 3135 2605 2255
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
100
580 435 350 215 145
150
875 655 525 325 215 160 130
200
875 700 435 290 215 175 145
350
765 510 380 305 255
500
730 545 435 365
800
875 700 580
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
100
290 215 175 105 70
150
435 325 260 160 105
200
435 350 215 145
350
380 255
500
365
800
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
100
500 390 325 280 215 175 145
150
750 585 485 420 325 260 215
200
1000 780 650 560 435 350 290
350
1755 1370 1140 985 765 610 510
500
2505 1955 1630 1410 1095 875 730
800
4010 3135 2605 2255 1750 1400 1165