Installation Typicals - Fastening on Steel Threaded Studs

DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEWFASTENER SYSTEM
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
Application
Fastening of cable trays, pipes on a horizontal cantilever support, fastened on
a horizontal structure
Support is fastened by two X-BT-MR (horizontal distance x)
L1 is the distance of the load center to the vertical structure surface
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of X-BT-MR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the
detailed statements in disclaimer 2018/05/04
Load F acting at the distance of L1 from structure surface
FASTENER TECHNICAL DETAILS
x
2 studs
per strut
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
125 100 85 60 40 30 25 20
100
145 120 100 70 50 40 30 25
125
165 140 120 85 60 45 40 30
150
180 155 135 100 70 55 45 40
175
195 170 150 110 80 65 50 45
200
205 180 160 120 90 70 60 50
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
505 310 210 150 115 65 35 15
100
630 385 265 190 140 80 45 20
125
790 485 330 240 180 100 55 25
150
950 580 400 290 215 125 70 30
175
1105 680 465 335 250 145 80 35
200
1265 775 530 385 285 165 90 40
NOTE: load capacity used for calculation N
rec
= 3.6 kN (axial) / V
rec
= 4.3 kN (shear)
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and X-BT-MR distance x)
FASTENING STRUT TO STEEL
WITH X-BT-MR*
Two X-BT-MR Threaded studs
X-BT-MR • Metric
*X-BT-MR is the new generation X-BT
17Issued August 2018, expiry January 2022