Installation Typicals - Fastening on Steel Threaded Studs

2 studs
4 studs
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEWFASTENER SYSTEM
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
x
x
Application
Fastening of cable trays, pipes on a T-Post support, which is fastened on a
horizontal structure
Support is fastened by two / four X-BT-MR (horizontal distance x)
L1 is the total width of the T-Post, L2 is fix set to 1000 mm
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of X-BT-MR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
2 Load cases: load asymmetric acting in the center of one arm only,
30% acting as horizontal load
FASTENER TECHNICAL DETAILS
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
4535 2970 2185 1715 1405
100
5670 3710 2735 2145 1755 1265
125
7085 4640 3415 2685 2195 1580
150
8505 5570 4100 3220 2635 1900 1460
175
9925 6500 4785 3760 3075 2215 1705 1360
200
11340 7425 5470 4295 3510 2535 1945 1555
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
150 150 150 150 150 150 150 150
100
180 180 180 180 180 180 180 180
125
215 215 215 215 215 215 215 215
150
240 240 240 240 240 240 240 240
175
270 270 270 270 270 270 270 270
200
290 290 290 290 290 290 290 290
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
85 85 85 85 85 85 85 85
100
100 100 100 100 100 100 100 100
125
125 125 125 125 125 125 125 125
150
145 145 145 145 145 145 145 145
175
165 165 165 165 165 165 165 165
200
180 180 180 180 180 180 180 180
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
2185 1405
100
2735 1755 1265
125
3415 2195 1580
150
4100 2635 1900 1460
175
4785 3075 2215 1705 1360
200
5470 3510 2535 1945 1555
NOTE: load capacity used for calculation N
rec
= 3.6 kN (axial) / V
rec
= 4.3 kN (shear)
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and X-BT-MR distance x)
FASTENING T-POST (CEILING) SUPPORT
WITH X-BT-MR*
Two / Four X-BT-MR Threaded studs
X-BT-MR • Metric
*X-BT-MR is the new generation X-BT
19Issued August 2018, expiry January 2022