Installation Typicals - Fastening on Steel Threaded Studs
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
FASTENING STRUT TO STEEL
WITH S-BT
Two S-BT-MR / S-BT-MF Threaded studs
Technical assessment — maximum of L1 and F (depending on load F or lever arm length L1 and S-BT distance x)
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
210 115 65 35 15
100
265 140 80 45 20
125
330 180 100 55 25
150
400 215 125 70 30
175
465 250 145 80 35
200
530 285 165 90 40
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
60 50 40 30 20 15 10 10
100
70 60 50 35 25 20 15 10
125
80 70 60 40 30 20 20 15
150
90 75 65 50 35 25 20 20
175
95 85 75 55 40 30 25 20
200
100 90 80 60 45 35 30 25
NOTE: load capacity used for calculation N
rec
= 1.8 kN (axial) / V
rec
= 2.6 kN (shear)
FASTENER OVERVIEW
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
S-BT-MR / S-BT-MF • Metric
x
2 studs
per strut
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Application
• Fastening of cable trays, pipes on a horizontal cantilever support, fastened on
a horizontal structure
• Support is fastened by two S-BT (horizontal distance x)
• L1 is the distance of the load center to the vertical structure surface
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of S-BT threaded stud. Structural
analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
• Load F acting at the distance of L1 from structure surface
31Issued August 2018, expiry January 2022