Installation Typicals - Fastening on Steel Threaded Studs

2 studs
4 studs
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
FASTENING T-POST (CEILING) SUPPORT
WITH S-BT
Two / Four S-BT-MR / S-BT-MF Threaded studs
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and S-BT distance x)
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
100
1265
125
1580
150
1900
175
2215 1360
200
2535 1555
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
2185 1405
100
2735 1755 1265
125
3415 2195 1580
150
4100 2635 1900 1460
175
4785 3075 2215 1705 1360
200
5470 3510 2535 1945 1555
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
40 40 40 40 40 40 40 40
100
50 50 50 50 50 50 50 50
125
60 60 60 60 60 60 60 60
150
70 70 70 70 70 70 70 70
175
80 80 80 80 80 80 80 80
200
90 90 90 90 90 90 90 90
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
75 75 75 75 75 75 75 75
100
90 90 90 90 90 90 90 90
125
105 105 105 105 105 105 105 105
150
120 120 120 120 120 120 120 120
175
135 135 135 135 135 135 135 135
200
145 145 145 145 145 145 145 145
NOTE: load capacity used for calculation N
rec
= 1.8 kN (axial) / V
rec
= 2.6 kN (shear)
FASTENER OVERVIEW
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
S-BT-MR / S-BT-MF • Metric
x
x
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Application
Fastening of cable trays, pipes on a T-Post support, which is fastened on a
horizontal structure
Support is fastened by two / four S-BT (horizontal distance x)
L1 is the total width of the T-Post, L2 is fix set to 1000 mm
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of S-BT threaded stud. Structural
analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer 2018/05/04
2 Load cases: load asymmetric acting in the center of one arm only,
30% acting as horizontal load
33Issued August 2018, expiry January 2022