Installation Typicals - Fastening on Steel Threaded Studs
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
4 studs
2 studs
1 stud
FASTENER OVERVIEW
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
x
x
2 studs
FASTENER SYSTEM
FASTENER TECHNICAL DETAILS
Application
• Fastening of cable trays, pipes on a horizontal, braced cantilever support,
fastened on a vertical structure
• Support is fastened by three / six X-BT-MF on both support and brace
baseplate with distance x
• L1 is the distance of the load center to the vertical structure surface, the angle
of the brace is 45°
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of X-BT-MF threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
• Shear load fully carried by one / two top X-BT-MF (worst-case)
• Load F acting at the distance of L1 from structure surface
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
100
295 220 175 110 70
150
445 335 265 165 110 80 65
200
445 355 220 145 110 85 70
350
390 260 195 155 130
500
370 280 220 185
800
445 355 295
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
100
470 365 305 260 210 175 145
150
705 550 455 395 315 265 220
200
940 735 610 525 425 355 295
350
1650 1285 1070 925 745 625 520
500
2355 1840 1530 1320 1060 895 745
800
3770 2945 2445 2115 1700 1435 1195
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
100
365 260 210 175 145 110
150
550 395 315 265 220 165
200
735 525 425 355 295 220
350
1285 925 74 5 625 520 390
500
1840 1320 1060 895 745 560
800
2945 2115 1700 1435 1195 895
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
100
145 110 85 55 35
150
220 165 130 80 55
200
220 175 110 70
350
195 130
500
185
800
NOTE: load capacity used for calculation N
rec
= 1.5 kN (axial) / V
rec
= 2.2 kN (shear)
Technical assessment — maximum of F (depending on load F or lever arm length L1 and baseplate distance x)
FASTENING BRACED CANTILEVER SUPPORT
WITH X-BT-MF
Two / Four X-BT-MF Threaded studs
X-BT-MF • Metric
44Issued August 2018, expiry January 2022