Installation Typicals - Fastening on Steel Threaded Studs
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEW
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
x
2 studs
per strut
FASTENER SYSTEM
FASTENER TECHNICAL DETAILS
Application
• Fastening of cable trays, pipes on a horizontal cantilever support, fastened on
a horizontal structure
• Support is fastened by two X-BT-MF (horizontal distance x)
• L1 is the distance of the load center to the vertical structure surface
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of X-BT-MF threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
• Load F acting at the distance of L1 from structure surface
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
50 40 35 25 15 10 10 5
100
60 50 40 30 20 15 10 10
125
65 55 50 35 25 20 15 10
150
75 65 55 40 30 20 15 15
175
80 70 60 45 30 25 20 15
200
85 75 65 50 35 30 25 20
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
160 80 40 15
100
205 100 50 20
125
255 125 65 25
150
305 155 75 30
175
360 180 90 35
200
410 205 105 40
NOTE: load capacity used for calculation N
rec
= 1.5 kN (axial) / V
rec
= 2.2 kN (shear)
Technical assessment — maximum of L1 and F (depending on load F or lever arm length L1 and X-BT-MF distance x)
FASTENING STRUT TO STEEL
WITH X-BT-MF
Two X-BT-MF Threaded studs
X-BT-MF • Metric
45Issued August 2018, expiry January 2022