Installation Typicals - Fastening on Steel Threaded Studs

FASTENER OVERVIEW
APPLICATION OVERVIEW
DISCLAIMERHOW TO USE THIS DOCUMENT
x
x
2 studs
4 studs
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Application
Fastening of cable trays, pipes on a horizontal cantilever support, fastened on
a vertical structure
Support is fastened by two / four X-ST-GR on both support and brace
baseplate with distance x
L1 is the distance of the load center to the vertical structure surface
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of X-ST-GR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer 2018/05/04
Shear load fully carried by one / two top X-ST-GR (worst-case)
Load F acting at the distance of L1 from structure surface
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
585 385 270 200 150 95 60 35
100
730 485 340 250 190 120 75 45
125
915 605 425 315 240 150 95 55
150
1100 730 510 375 290 180 110 70
175
1280 850 595 440 335 210 130 80
200
1465 970 680 500 385 240 150 90
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
150 125 105 70 45 35 25 20
100
175 145 125 85 60 45 35 30
125
200 165 145 100 75 55 45 35
150
220 185 165 120 85 65 55 45
175
235 205 180 130 95 75 60 50
200
250 220 195 145 110 85 70 60
Result:
Load
F [kg]
L1 [m m]
150 200 250 400 600 800 1000 1200
x
[mm]
80
75 60 50 35 20 15 10 10
100
85 70 60 40 30 20 15 15
125
100 80 70 50 35 25 20 15
150
110 90 80 60 40 30 25 20
175
115 100 90 65 45 35 30 25
200
125 110 95 70 55 40 35 30
Result:
L1 [mm]
F [kg]
50 75 100 125 150 200 250 300
→ Load in [kN] 0.49 0.74 0.98 1.23 1.47 1.96 2.45 2.94
x
[mm]
80
270 150 95 60 35
100
340 190 120 75 45
125
425 240 150 95 55
150
510 290 180 110 70
175
595 335 210 130 80
200
680 385 240 150 90
NOTE: load capacity used for calculation N
rec
= 1.8 kN (axial) / V
rec
= 1.8 kN (shear)
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and X-ST-GR distance x)
FASTENING CANTILEVER SUPPORT
WITH X-ST-GR
Two / Four X-ST-GR Threaded studs
X-ST-GR • Metric
57