Installation Typicals - Fastening on Steel Threaded Studs

2 studs
4 studs
APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMERFASTENER TECHNICAL DETAILS
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG) FASTENER OVERVIEWFASTENER SYSTEM
x
x
Application
Fastening of cable trays, pipes on a T-Post support, which is fastened on a
horizontal structure
Support is fastened by two / four X-BT-MR (horizontal distance x)
L1 is the total width of the T-Post, L2 is fix set to 1000 mm
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of X-BT-MR threaded stud.
Structural analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer — 2018/05/04
2 Load cases: load asymmetric acting in the center of one arm only,
30% acting as horizontal load
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
188.00 123.25 91.00 58.50
4.0
250.75 164.50 121.25 78.25 56.50
5.0
313.50 205.75 151.75 97.75 70.75 54.50
6.0
376.25 246.75 182.00 117.25 85.00 65.50
7.0
439.00 288.00 212.50 137.0 0 99.25 76.50 61.50
8.0
501.75 329.25 242.75 156.50 113.25 87.50 70.25
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
312 312 312 312 312 312 312 312
4.0
385 385 385 385 385 385 385 385
5.0
448 448 448 448 448 448 448 448
6.0
502 502 502 502 502 502 502 502
7.0
550 550 550 550 550 550 550 550
8.0
593 593 593 593 593 593 593 593
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
172 172 172 172 172 172 172 172
4.0
218 218 218 218 218 218 218 218
5.0
260 260 260 260 260 260 260 260
6.0
297 297 297 297 297 297 297 297
7.0
332 332 332 332 332 332 332 332
8.0
363 363 363 363 363 363 363 363
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
91.00 58.50
4.0
121.25 78.25 56.50
5.0
151.75 97.75 70.75
6.0
182.00 117. 25 85.00
7.0
212.50 137.0 0 99.25 61.50
8.0
242.75 156.50 113.25 70.25
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and X-BT-MR distance x)
FASTENING T-POST (CEILING) SUPPORT
WITH X-BT-MR*
Two / Four X-BT-MR Threaded studs
X-BT-MR • Imperial
*X-BT-MR is the new generation X-BT
NOTE: load capacity used for calculation N
rec
= 810 lb (axial) / V
rec
= 970 lb (shear)
75Issued August 2018, expiry January 2022