Installation Typicals - Fastening on Steel Threaded Studs
APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMER
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
FASTENING STRUT TO STEEL
WITH S-BT
Two / Four S-BT-MR / S-BT-MF Threaded studs
Technical assessment — maximum of L1 and F (depending on load F or lever arm length L1 and S-BT distance x)
FASTENER OVERVIEW
S-BT-MR / S-BT-MF • Imperial
x
2 studs
per strut
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
195 117 83 65 53 45 39 34
4.0
234 146 106 83 69 58 51 45
5.0
265 172 127 101 83 71 62 55
6.0
292 195 146 117 97 83 73 65
7.0
315 215 164 132 110 95 83 74
8.0
334 234 180 146 123 106 93 83
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
14.50 8.50 5.75 2.75 1.25 0.50
4.0
19.25 11.50 7.50 3.75 1.75 0.50
5.0
24.00 14.25 9.50 4.50 2.25 0.75
6.0
29.00 17.25 11.50 5.50 2.75 1.00
7.0
33.75 20.25 13.25 6.50 3.00 1.00
8.0
38.75 23.00 15.25 7.50 3.50 1.25
Application
• Fastening of cable trays, pipes on a horizontal cantilever support, fastened on a
vertical structure
• Support is fastened by two S-BT (horizontal distance x)
• L1 is the distance of the load center to the center of the fasteners
• Load F is the acceptable total load (all dead load including)
Boundary conditions
• These values are ONLY reflecting capacity of S-BT threaded stud. Structural
analysis of support / structure is NOT in Hilti scope. See the detailed statements in
disclaimer — 2018/05/04
• Shear load fully carried by one S-BT (worst-case)
• Load F acting at the distance of L1 from structure surface
NOTE: load capacity used for calculation N
rec
= 405 lb (axial) / V
rec
= 585 lb (shear)
88Issued August 2018, expiry January 2022