Installation Typicals - Fastening on Steel Threaded Studs

2 studs
4 studs
APPLICATION OVERVIEW HOW TO USE THIS DOCUMENT DISCLAIMER
DOWNLOAD DRAWINGS (PDF) DOWNLOAD DRAWINGS (DWG)
FASTENING T-POST (CEILING) SUPPORT
WITH S-BT
Two / Four S-BT-MR / S-BT-MF Threaded studs
Technical assessment maximum of L1 and F (depending on load F or lever arm length L1 and S-BT distance x)
NOTE: load capacity used for calculation N
rec
= 450 lb (axial) / V
rec
= 585 lb (shear)
FASTENER OVERVIEW
S-BT-MR / S-BT-MF • Imperial
x
x
FASTENER TECHNICAL DETAILS
FASTENER SYSTEM
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
91.00 58.50
4.0
121.25 78.25 56.50
5.0
151.75 97.75 70.75
6.0
182.00 117. 25 85.00
7.0
212.50 137.00 99.25 61.50
8.0
242.75 156.50 113.25 70.25
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
157 157 157 157 157 157 157 157
4.0
194 194 194 194 194 194 194 194
5.0
226 226 226 226 226 226 226 226
6.0
255 255 255 255 255 255 255 255
7.0
279 279 279 279 279 279 279 279
8.0
301 301 301 301 301 301 301 301
Result:
Load
F [lbs]
L1 [inch]
6.0 12.0 18.0 24.0 30.0 36.0 42.0 48.0
x
[inch]
3.0
87 87 87 87 87 87 87 87
4.0
110 110 110 110 110 110 110 110
5.0
132 132 132 132 132 132 132 132
6.0
151 151 151 151 151 151 151 151
7.0
169 169 169 169 169 169 169 169
8.0
185 185 185 185 185 185 185 185
Result:
L1 [inch]
F [lbs]
100 150 200 300 400 500 600 700
x
[inch]
3.0
4.0
56.50
5.0
70.75
6.0
85.00
7.0
99.25 61.50
8.0
113.25 70.25
Application
Fastening of cable trays, pipes on a T-Post support, which is fastened on a
horizontal structure
Support is fastened by two / four S-BT (horizontal distance x)
L1 is the total width of the T-Post, L2 is fix set to 1000 mm
Load F is the acceptable total load (all dead load including)
Boundary conditions
These values are ONLY reflecting capacity of S-BT threaded stud. Structural
analysis of support / structure is NOT in Hilti scope. See the detailed
statements in disclaimer 2018/05/04
2 Load cases: load asymmetric acting in the center of one arm only,
30% acting as horizontal load
89Issued August 2018, expiry January 2022