Product Data Sheet for CFS-CID 8” and 10”

Product Information
Hilti Firestop
Saving lives
through innovation
and education
DBS • 06/18
Hilti, Inc. (U.S.)
1-800-879-8000 | en español 1-800-879-5000
www.hilti.com
Hilti (Canada) Corporation
1-800-363-4458
www.hilti.ca
CFS-CID P 8 AND 10
CFS-CID M 8 AND 10
Product description
Firestop cast-in device for 8’’ and 10’’ metallic pipes, and plastic or insulated
metal
Five heights available (6’’, 8’’, 10’’, 12’’ and 14’)
Product features
Increased productivity and reduced labor costs
Simple and quick installation
No need for large firestop collars requiring two pairs of hands to install
Meets OSHA part 1926 lid requirements
Single manufacturer covering most vertical pipe applications
Advantages
One-step firestop solution for 8” and 10” plastic pipes and 4”, 6” and 8” metal
pipes with insulation
One-step firestop solution for 8” and 10” metal pipes
Increased productivity helps reduce cost
Quick and simple installation
Reduces the chance of project delays due to failed inspections
UL and FM approved firestop device
Available in five different heights
Applications
For use with new building construction (flat concrete)
For use with PVC pipe (CFS-CID P 8” and CFS-CID P 10”)
For use with metal pipes with insulation (CFS-CID P 8” and CFS-CID P 10”)
For use with metal pipes (CFS-CID M 8” and 10”)
Available in 6”, 8”, 10”, 12”, 14” heights
Installation instructions
See Hilti literature or third-party listings for complete application and installation
details
Technical Data
Base Material
Concrete
Approvals
UL and FM
Tested in accordance with
ASTM E814, UL 1479 and CAN/ULC-S115
Application temperature range
-40 °F to 120 °F
Intumescent
Yes
Mold and Mildew resistance
Yes
Mold and Mildew performance
Class 0 (ASTM G21-96)
Reusable (and removable)
Not possible
Smoke and gas resistant
Yes
W-rating
Yes (additional steps required)
Product Footprint Max pipe OD
CFS-CID P 8”
14.6 8.625”
CFS-CID P 10”
18.7 10.750”
CFS-CID M 8”
11.6 8.625”
CFS-CID M 10”
14.0 10.750”
FIRESTOP DEVICE
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY 5N76