IAPMO ER-678 KB1 Expansion Anchor Concrete

Number: 678
Originally Issued: 11/23/2020 Revised: 03/16/2021 Valid Through: 11/30/2022
The product described in this Uniform Evaluation Service (UES) Report has been evaluated as an alternative material, design or method of construction in order to satisfy and comply with
the intent of the provision of the code, as noted in this report, and for at least equivalence to that prescribed in the code in quality, strength, effectiveness, fire resistance, durability and safety,
as applicable, in accordance with IBC Section 104.11. This document shall only be reproduced in its entirety.
Copyright © 2021 by International Association of Plumbing and Mechanical Officials. All rights reserved. Printed in the United States. Ph: 1-877-4IESRPT • Fax: 909.472.4171
web: www.uniform-es.org • 4755 East Philadelphia Street, Ontario, California 91761-2816 USA
Page 1 of 10
HILTI, INC.
7250 Dallas Parkway
Suite 1000
Plano, TX 75024
(800) 879-8000
www.hilti.com
hiltitecheng@hilti.com
HILTI
®
KB1 EXPANSION ANCHORS FOR USE
IN CRACKED AND UNCRACKED CONCRETE
CSI Division:
03 00 00CONCRETE
05 00 00METALS
CSI Section:
03 16 00Concrete Anchors
05 05 19Post-installed Concrete Anchors
1.0 RECOGNITION
HILTI KB1 Expansion Anchors recognized in this report
have been evaluated for use as torque-controlled,
mechanical expansion anchors. The structural performance
properties of the HILTI KB1 Expansion Anchors comply
with the intent of the provisions of the following codes and
regulations:
2021, 2018, 2015, and 2012 International Building
Code
®
(IBC)
2021, 2018, 2015, and 2012 International
Residential Code
®
(IRC)
2020 City of Los Angeles Building Code (LABC)
attached Supplement
2020 City of Los Angeles Residential Code
(LARC) attached supplement
2020 Florida Building Code, Building (FBC
Building) attached supplement
2020 Florida Building Code, Residential (FBC
Residential) attached supplement
1.0 LIMITATIONS
Use of the HILTI KB1 Expansion Anchors recognized in
this report is subject to the following limitations:
2.1 The anchors shall be installed in accordance with the
IBC or IRC, this report, and the manufacturer’s printed
installation instructions (MPII). Where conflicts occur, the
more restrictive governs.
2.2 The anchor sizes, dimensions, and minimum
embedment depths shall be as set forth in this report.
2.3 The anchors shall be installed in cracked and
uncracked normal-weight or lightweight concrete having a
specified compressive strength, f’
c
, between 2,500 psi (17.2
MPa) and 8,500 psi (58.6 MPa), and cracked and uncracked
normal-weight or sand-lightweight concrete over metal deck
having a minimum specified compressive strength, f’
c
, of
3,000 psi (20.7 MPa).
2.4 For calculation purposes, the compressive strength
value, f’
c
, shall not exceed 8,000 psi (55.2 MPa).
2.5 Strength design values shall be determined in
accordance with Section 3.2.1 of this report. Loads applied
to the anchors shall be adjusted in accordance with Section
1605.2 of the IBC for strength design.
2.6 Allowable stress design values shall be determined in
accordance with Section 3.2.2 of this report. Loads applied
to the anchors shall be adjusted in accordance with Section
1605.3 of the IBC.
2.7 Anchor spacing, edge distance and minimum concrete
thickness shall comply with Table 3 of this report.
2.8 Prior to installation, calculations and design details
that demonstrate compliance to this report shall be
submitted to the building official. The calculations and
design details shall be prepared by a registered design
professional where required by the laws and statutes of the
jurisdiction in which the construction is to occur.
2.9 Since suitable criteria for evaluating performance is
not available, the use of the subject anchors for fatigue or
shock loading conditions is beyond the scope of this report.
2.10 Use of zinc-plated carbon steel anchor is limited to
dry, interior locations.
2.11 Periodic special inspection shall be provided in
accordance with Section 3.4 of this report.
2.12 Where not otherwise prohibited in the applicable code,
anchors permitted for use with fire-resistant-rated
construction provided at least one of the following
conditions is satisfied:
Anchors are used to resist wind or seismic forces
only.
Anchors that support fire-resistance-rated
construction or gravity load-bearing structural
elements are within a fire-resistance-rated
envelope or a fire-resistance membrane, are
protected by approved fire-resistance-rated
materials, or have been evaluated for resistance to
fire exposure in accordance with recognized
standards.
Anchors are used to support nonstructural
elements.