Product Data Sheet for CFS-CID MD
Hilti Firestop
Saving lives
through innovation
and education
Product Information
DBS • 08/19
Technical Data
Devices
CFS CID MD P/M 2”
CFS CID MD P/M 3”
CFS-CID MD P/M 4”
Footprint
3-3/4” x 4-1/2”
4-3/4”x5-5/8”
6-3/8” x 6-3/4”
Base Material
Concrete over Metal Deck
Application temperature
Min 23 °F (-5 °C) / Max 122 °F (50 °C)
Expansion temperature
410 °F (210 °C)
Expansion rate
1:19 (Unrestricted)
Standard heights
2.5" & 4"
Temperature resistance
Maximum 212 °F (100 °C)
Color
CFS CID MD P: Red
CFS CID MD M: Black
Tested in accordance with
UL 1479, ASTM E 814, ASTM G21
FIRESTOP CAST-IN DEVICES FOR
METAL DECK (CFS-CID MD)
Application
• Opening creation in corrugated metal deck slabs to run pipes or conduits
• Sealing combustible and non-combustible penetrations
• Designed to work in composite W3 and W2 floor decks for a wide number of
manufacturers
• For slab thicknesses from 2.5” up to 6” from top of the deck
• Concrete floor assemblies rated up to 3 hours
Product Benefit and Features
• Quick and simple installation — designed to increase your productivity and
reduce labor costs
• Peace of mind — cast-in devices remove scope for errors compared
to traditional methods, leading to more reliable firestopping of vertical
penetrations
• Creates an opening with the firestop already included — no coming back for
firestopping required
• Integrated moisture and smoke seal — no additional backfilling required
• No steel deck reinforcement or additional shoring needed to support the steel
deck as a form during the construction phase
• Deck is cut after concrete is cured and it does not interfere with reinforcement
• No need of torches, plasma cutters or core rigs to perform the penetrations
Installation instructions
• See Hilti Literature or third-party listings for complete application and
installation details
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Accessories:
• Metal Deck Platforms, CFS CID MD PLT W3 and W2
• Metal Deck Guide Sleeve, CFS CID MD HS GUI 2” / 3” / 4”
• Metal Deck Hole Saw, CFS CID MD HS 2” / 3” / 4”
• Supporting Shaft, CFS CID ARB TE-Y / TE-C
Platforms Hole saws Guide sleeves Shafts
Material
20 ga steel galvanized sheet metal galvanized steel
Dimensions
12” long 7” wide OD (Size of cut) height 6” 450 mm long
Feature
Quick Insert Quick Insert
Technology
Carbide teeth
Mold and Mildew resistance
Yes, per ASTM G21
Base Material
W3” & W2” metal floor decking Metal
Connection-end
TE-C (SDS PLUS) & TE-Y (SDS MAX)