Offset and DifferentialOffset and Differential
Offset:
The point above (cool) or below (heat) target temperature where the
stage turns off.
Differential:
The difference in degrees between the temperature a stage comes on
and the temperature the stage goes off.
Examples
Heat Mode:
If the Target Temp is set at 80 degrees, Offset set at 4 degrees, and
Differential set at 2 degrees, The System will engage Heat Mode when
building temperature reaches 74 degrees and the curtains are closed.
Example: Target
Temp
- Offset - Differential = Heat Mode on
80 - 4 - 2 = 74