System 1000 Power VentSystem 1000 Power Vent Offset and DifferentialOffset and Differential 1414
If the Target Temp is set at 80 degrees, Offset at 4 degrees and
Differential set at 2 degrees, The System will disengage Heat Mode
when building temperature reaches 76 degrees.
Example: Target Temp - Offset = Heat Mode Off
80 - 4 = 76
Cool Mode:
If the Target Temp is set at 80 degrees, Offset set at 5 degrees, and
Differential set at 2 degrees, The System will engage the fans when
building temperature reaches 87 degrees.
Example: Target Temp + Offset + Differential = Cool Mode On
80 + 5 + 2 = 87
If the Target Temp equals 80 degrees, Offset equals 5 degrees, and
Differential equals 2 degrees, The System will disengage the fans when
building temperature reaches 85 degrees.
Target Temp + Offset = Cool Mode Off
Example: 80 + 5 = 85