attach contacts to the position marked "NC". If your alarm is a "normally
open" system, use the position marked "NO".
9. Apply power to the system.
Set points
The unit allows the operator to set the system according to his or her needs. Set
points can be changed as often as desired. The range of these set points are as
follows:
Feature Minimum Maximum
High end temperature
High end pressure
Low end temperature
Low end pressure
High pressure alarm
Low pressure alarm
Differential
20
o
F
0 "w.c.
0
o
F
0 "w.c.
.0500 "w.c.
0 "w.c.
.0100 "w.c.
100
o
F
.2000 "w.c.
100
o
F
.2000 "w.c.
.2000 "w.c.
.1000 "w.c.
.1500 "w.c.
Minimum pressure
Timer period
Vent time delay
.0100 "w.c.
1 min
0 sec.
.2000 "w.c.
30 min
300 sec.
Recommended Wire Gauge for LOW VOLTAGE hookup.
Component HHI Wiring Part No. Recommended Wire
Sensor 1502-2427 18/2 Shielded Cable
Hall Effect Devices 1502-2427 18/2 Shielded Cable
PVR-H 1503-1508 18/3 Cable SJT