Instruction Manual Inverter L2002

“B” Group: Fine Tuning Functions
Configuring
Drive Parameters
3–42
B091/B088: Stop Mode / Restart Mode Configuration – You can configure how the
inverter performs a standard stop (each time Run FWD and REV signals turn OFF).
Setting B091 determines whether the inverter will control the deceleration, or whether it
will perform a free-run stop (coast to a stop). When using the free-run stop selection, it is
imperative to also configure how you want the inverter to resume control of motor speed.
Setting B088 determines whether the inverter will ensure the motor always resumes at
0 Hz, or whether the motor resumes from its current coasting speed (also called
frequency matching). The Run command may turn OFF briefly, allowing the motor to
coast to a slower speed from which normal operation can resume.
“B” Function Run
Mode
Edit
Lo Hi
Defaults
Func.
Code
Name /
SRW Display
Description
–FE(F)
(EU)
–FU
(USA)
Units
B080 [AM] analog signal
gain
Adjust of analog output at
terminal [AM],
range is 0 to 255
✔ ✔ 100. 100.
AM-Adj 00100%
B082 Start frequency adjust-
ment
Sets the starting frequency for
the inverter output, range is 0.5
to 9.9 Hz
✘ ✔ 0.5 0.5 Hz
fmin 0000.5Hz
B083 Carrier frequency
setting
Sets the PWM carrier (internal
switching frequency), range is
2.0 to 14.0 kHz
✘ ✘ 5.0 5.0 kHz
Carrier 0005.0
B084 Initialization mode
(parameters or trip
history)
Select the type of initialization
to occur, two option codes:
00... Trip history clear
01... Parameter initialization
02... Trip history clear and
parameter initialization
✘ ✘ 00 00
INIT Mode TRP
B085 Country code for initial-
ization
Select default parameter values
for country on initialization,
four options, option codes:
00... Japan version
01... Europe version
02... US version
✘ ✘ 01 02
INIT Slct USA
B086 Frequency scaling
conversion factor
Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
✔ ✔ 1.0 1.0
Cnv Gain 0001.0
B087 STOP key enable Select whether the STOP key
on the keypad is enabled, two
option codes:
00... enabled
01... disabled
✘ ✔ 00 00
STP Key ON