Network Card User Manual

Appendix
Page 21 of 36
Appendix – Parameter List
Note: Parameters in BOLDFACE can be edited while inverter is in the RUN mode. “RO” means the
parameter is Read Only, and “R/W” means the value can be read or written.
Inverter
Parameter
Modbus
Start
Address
Modbus
End
Address
Parameter Name
Magnitude
Read/
Write
Data Range
D – Monitoring Functions
D001 3001 3002 Output frequency monitor X1000 RO 0 – 400000
D002 3003 3004 Output current monitor X10 RO 0 – 10000
D003 3005 3006 Rotation direction monitor X1 RO 0 – 2
D004 3007 3008
Process Variable (PV) PID
feedback monitor
X100 RO 0 – 999900
D005 3009 3010 Intelligent input terminal status X1 RO 0 – 65535
D006 3011 3012 Intelligent output terminal status X1 RO 0 – 65535
D007 3013 3014 Scaled output frequency monitor X1000 RO 0 – 39960000
D012 3023 3024 Output torque monitor X1 RO –300 – 300
D013 3025 3026 Output voltage monitor X10 RO 0 – 10000
D014 3027 3028 Input electric power monitor X10 RO 0 – 10000
D016 3031 3032 Cumulative RUN time monitor X1 RO
0 –
4294836225
D017 3033 3034 Cumulative power–on time X1 RO
0 –
4294836225
D080 3159 3160 Trip counter X1 RO 0 – 65535
D078 3155 3156 Last trip pointer X1 RO 0 – 5
D081 3161 3162 Error Code of Trip 1 X1 RO 0 – 255
D355 3709 3710 Frequency at Trip 1 X100 RO 0 – 40000
D356 3711 3712 Output current at Trip 1 X10 RO 0 – 10000
D357 3713 3714 PN voltage (DC voltage) at Trip 1 X10 RO 0 – 10000
D358 3715 3716 Cumulative RUN time at Trip 2 X1 RO
0 –
4294836225
D359 3717 3718 Cumulative power–on time at Trip 2 X1 RO
0 –
4294836225
D082 3163 3164 Error Code of Trip2 X1 RO 0 – 255
D361 3721 3722 Frequency at Trip 2 X100 RO 0 – 40000
D362 3723 3724 Output current of Trip 2 X10 RO 0 – 10000
D363 3725 3726 PN voltage (DC voltage) at Trip2 X10 RO 0 – 10000
D364 3727 3728 Cumulative RUN time at Trip 2 X1 RO
0 –
4294836225
D365 3729 3730 Cumulative power–on time at Trip 2 X1 RO
0 –
4294836225
D083 3165 3166 Error Code of Trip 3 X1 RO 0 – 255