User Manual

Chapter 8 Communication Functions
8 - 24
ii) List of warning data
Modbus
data
Operator
display
Condition
1
 Frequency upper limit setting (A061)Maximum frequency setting (A004)
2
 Frequency lower limit setting (A062)Maximum frequency setting (A004)
3

Output frequency setting (F001),
multispeed 0 (A020) (note 1)
Maximum frequency setting (A004)
10

Output frequency setting (F001),
multispeed 0 (A020) (note 1)
Frequency upper limit setting (A061)
17
 Fequency lower limit setting (A062)
Output frequency setting (F001), multispeed 0
(A020) (note 1)
23
 Start frequency adjustment (b082)Frequency upper limit setting (A061)
25
 Start frequency adjustment (b082)Fequency lower limit setting (A062)
27
 Start frequency adjustment (b082)
Output frequency setting (F001), multispeed 0
(A020) (note 1)
30
 Start frequency adjustment (b082)Jog frequency setting (A038)
31

Output frequency setting (F001),
multispeed 0 (A020) (note 1)
Jump (center) frequency settings 1/2/3 ± " Jump
(hysteresis) frequency width settings 1/2/3"
A063 ± A064, A065 ± A066, A067 ± A068
33

Multispeed 1 to 7 settings (A021 to
A027)
34
 Free-setting V/f frequency (7) (b112)Frequency upper limit setting (A061)
36
 Free-setting V/f frequency (7) (b112)Fequency lower limit setting (A062)
38
 Free-setting V/f frequency (7) (b112)
Output frequency setting (F001), multispeed 0
(A020) (note 1)
5
 Frequency upper limit setting (A261)Maximum frequency setting (A204)
6
 Frequency lower limit setting (A262)Maximum frequency setting (A204)
7

Output frequency setting (F001),
multispeed 0 (A220) (note 1)
Maximum frequency setting (A204)
14

Output frequency setting (F001),
multispeed 0 (A220) (note 1)
Frequency upper limit setting (A261)
21
 Fequency lower limit setting (A262)
Output frequency setting (F001), multispeed 0
(A220) (note 1)
24
 Start frequency adjustment (b082)Frequency upper limit setting (A261)
26
 Start frequency adjustment (b082)Fequency lower limit setting (A262)
28
 Start frequency adjustment (b082)
Output frequency setting (F001), multispeed 0
(A220) (note 1)
32

Output frequency setting (F001),
multispeed 0 (A220) (note 1)
Jump (center) frequency settings 1/2/3 ± " Jump
(hysteresis) frequency width settings 1/2/3"
A063 ± A064, A065 ± A066, A067 ± A068
35
 Free-setting V/f frequency (7) (b112)Frequency upper limit setting (A261)
37
 Free-setting V/f frequency (7) (b112)Fequency lower limit setting (A262)
39
 Free-setting V/f frequency (7) (b112)
Output frequency setting (F001), multispeed 0
(A220) (note 1)
Note) The warning data of the Modbus communication do not accord with the warning cord of the
operator.

























