User Manual

Chapter 8 Communication Functions
8 - 33
Register
No.
Function name
Function
code
R/W Monitoring and setting items
Data
resolution
1342h to
1348h
(Reserved) - - -
1349h
Operation level at O
disconnection
b070 R/W
0. to 100. (%) or "no" (ignore)
1 [%]
134Ah to
1350h
(reserved) - - - -
1351h
Cumulative input power data
clearance
b078 R/W Clearance by setting "1" -
1352h Watt-hou
r
display gain b079 R/W 1 to 1000 1
1353h to
1354h
(Reserved) - - - -
1355h Start frequency b082 R/W 1 to 999 0.01 [Hz]
1356h Carrier frequency b083 R/W 20 to 150 0.1 [kHz]
1357h
Initialization mode (parameters or
trip history)
b084 R/W
0(disabling),1 (clearing the trip history),
2 (initializing the data), 3 (clearing the
trip history and initializing the data)
-
1358h Country code for initialization b085 R/W 0 (area A), 1 (area B), 3(area D) -
1359h
Frequency scaling conversion
facto
r
b086 R/W 1 to 9999 0.01
135Ah STOP key enable b087 R/W
0 :ON(enabling),
1 :OFF (disabling),
2 :Only Reset(disabling only stop)
-
135Bh Restart mode after FRS b088 R/W
0 (starting with 0 Hz), 1 (starting with
matching frequency)
-
135Ch
Automatic carrier frequency
reduction
b089 R/W
0(disabling)/1(enabling( output current
controlled))
-
135Dh (Reserved) - - - -
135Eh Stop mode selection b091 R/W
0 (deceleration until stop), 1 (free-run
stop)
-
135Fh (Reserved) - - - -
1360h
(Reserved) - - - -
1361h
Initialization target data
b094 R/W
0(All parameter)
/1(expect terminal and communication)
-
1362h to
1366h
(Reserved) - - - -
1367h Free-setting V/f frequency (1) b100 R/W 0. to "free-setting V/f frequency (2)" 1 [Hz]
1368h Free-setting V/f voltage (1) b101 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]
1369h Free-setting V/f frequency (2) b102 R/W 0. to "free-setting V/f f
r
equency (3)" 1 [Hz]
136Ah Free-setting V/f voltage (2) b103 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]
136Bh Free-setting V/f frequency (3) b104 R/W 0. to "free-setting V/f frequency (4)" 1 [Hz]
136Ch Free-setting V/f voltage (3) b105 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]
136Dh Free-setting V/f frequency (4) b106 R/W 0. to "free-setting V/f frequency (5)" 1 [Hz]
136Eh Free-setting V/f voltage (4) b107 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]
136Fh Free-setting V/f frequency (5) b108 R/W 0. to "free-setting V/f frequency (6)" 1 [Hz]
1370h Free-setting V/f voltage (5) b109 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]
1371h Free-setting V/f frequency (6) b110 R/W 0. to "free-setting V/f frequency (7)" 1 [Hz]
1372h Free-setting V/f voltage (6) b111 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]
1373h Free-setting V/f frequency (7) b112 R/W 0. to 400. 1 [Hz]
1374h Free-setting V/f voltage (7) b113 R/W 200V:0. to 3000 400 V:0. to 6000 0.1 [V]